Page 107
TITANUS
PRO·SENS
®
TECHNICAL MANUAL
6.5
Filter
6.5.1
Installation of the air Filter type LF-AD-x
Fig. 6.7: Distances of the drill holes in the bottom of the air filter housing
Air filter LF-AD-x
1.
To fit the filter into the pipe systems use the two PG29-screw joints of
the
filter.
2. Mount these screw joints like e.g. at the pipe adapter.
3. When mounting the filter pay attention to the direction of the air flow
indicated on the type plate in the housing bottom.
4. Screw the bottom side of the air filter housing directly to a wall.
Mounting Material
Air Filter
cylinder or flat head screws
– thread diameter max. 4 mm
– head diameter: 5 to 7 mm