C-2 | Thermox CEM Humox Analyzer
To determine the minimum external voltage supply required to power the current
outputs, use the following formula:
VEXTmin = .02 amps (RLoad + Rwires) + 4 volts
where:
VEXTmin = the minimum external voltage required to power
current output circuit
RLoad = the load resistance of the current output device
Rwires = the resistance of the wires