ASCO MECHANICAL GAS VALVES
All Amerex Kitchen Fire Suppression Systems that protect any gas
fired cooking appliance must use a “pull to close” type gas shut-off
valve, which is listed with the system. The valve is held open with a
latching device. Upon system discharge a piston in the gas trip
assembly (sold separately) will pull on a cable connected to the latch
on the gas valve, release the latch and allow the spring in the valve
to close the valve. The ASCO gas shut-off valves approved for use
with Amerex Kitchen Fire Suppression Systems are listed below with
appropriate part numbers. See “Installing a Mechanical Gas Valve”
in the Installation section for instruction on installation.
Note:
P/N 12740 Gas Trip Assembly must be purchased separately.
APPLICATIONS
Amerex
Part No.
ASCO Part No.
Size
13777
JV216-587-2
¾”
13778
JV216-587-3
1”
13779
JV216-587-4
1¼”
13780
JV216-587-5
1½”
13781
JV216-587-6
2”
*13782
JV216-587-7
2½”
*13783
JV216-587-8
3”
*Item in stock at Amerex – Trussville, AL
ANSUL MECHANICAL GAS SHUT-OFF VALVES
All Amerex Kitchen Fire Suppression Systems that protect
any gas fired cooking appliance must use a “pull to close”
type gas shut-off valve. The valve is held open with a
latching device. Upon system discharge a piston in the
gas trip assembly will pull on a cable connected to the
latch on the gas valve, release the latch and allow the
spring in the valve to close the valve. Ansul’s mechanical
gas shut-off valves are suitable for use with Amerex
Kitchen Fire Suppression Fire Suppression system.
These valves, when used in conjunction with P/N 12740
Gas Trip Assembly, perform the same functions as
Amerex’s gas shut-off valves. The part numbers of the
valves acceptable for this use are listed below. They are
intended to be installed using the same installation
instruction as Amerex’s gas shut-off valves; see Installing
a Mechanical Gas Valve in the installation section for
instruction on installation.
NOTE:
P/N 12740 gas trip assembly must be purchased
separately.
December 2008
Section 2 System Components Page 2 – 13
Amerex KP Wet Chemical System (EX 4658)
APPLICATIONS
Ansul Part No.
Size
Max. Operating
Pressure
55598
¾”
55601
1”
10 PSI
55604
1¼”
(69 kPa)
55607
1½”
55610
2”
Содержание 20150
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 12: ......
Страница 21: ......
Страница 43: ......
Страница 99: ......
Страница 101: ......
Страница 134: ......
Страница 140: ......
Страница 145: ......
Страница 156: ...December 2008 Section 7 Reset and Recharge Page 7 8 Amerex Restaurant Fire Suppression System EX 4658 ...
Страница 159: ......
Страница 171: ...APPENDIX C MANUAL P N 26692 AMEREX STRIKETM ECS INSTALLATION OPERATION MAINTENANCE MANUAL February 2019 ...