December 2008
Section 3
ZD Design
Page 3 – 43
Amerex Restaurant Fire Suppression System (EX 4658)
ZONE DEFENSE DESIGN
THOSE INDIVIDUALS RESPONSIBLE FOR THE DESIGN & INSTALLATION OF THE AMEREX
“ZONE DEFENSE” RESTAURANT FIRE SUPPRESSION SYSTEM MUST BE TRAINED BY
AMEREX AND HOLD A CURRENT AMEREX CERTIFICATE OF TRAINING.
SYSTEM DESIGN
It is essential that any pre-engineered restaurant fire suppression system be properly designed, sized and
installed. This section covers the design aspects unique to the Amerex “Zone Defense” Restaurant Fire
Suppression System. The sketch below shows a typical Zone Defense System installed.
EXHAUST DUCT PROTECTION
The criteria for duct protection in a ZD System are the same as that for the KP System found in the
first half of this section.
PLENUM PROTECTION
The criteria for plenum protection in a ZD System are the same as that for the KP System found in
first half of this section.
DEDICATED APPLIANCE PROTECTION
When a ZD System includes protection for an appliance which
cannot
be protected by the ZD
Nozzles creating the “zone of defense”, that appliance is to be protected using Dedicated Appliance
Protection. The Dedicated Appliance Protection is found in the preceding portion of this section.
Содержание 20150
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 12: ......
Страница 21: ......
Страница 43: ......
Страница 99: ......
Страница 101: ......
Страница 134: ......
Страница 140: ......
Страница 145: ......
Страница 156: ...December 2008 Section 7 Reset and Recharge Page 7 8 Amerex Restaurant Fire Suppression System EX 4658 ...
Страница 159: ......
Страница 171: ...APPENDIX C MANUAL P N 26692 AMEREX STRIKETM ECS INSTALLATION OPERATION MAINTENANCE MANUAL February 2019 ...