February 2019
Section 4 Installation
Page 4
-
14b
Amerex Restaurant Fire Suppression System
(EX 4658)
Linear Actuator Installation
The Linear Actuator is used in conjunction with the STRIKE™ ECS and is for UL Certification
only and cannot be considered for or used in installations of KP/ZD systems in Canada.
Linear Actuators (P/N 24448) are used for actuation of an STRIKE™ Releasing Module. The
STRIKE™ ECS supports up to two actuation circuits and therefore up to two Linear Actuators. All
Linear Actuators must be installed in accordance with the following instructions.
Do NOT connect
any field wiring to installed Linear Actuators until directed to do so in the STRIKE™ ECS
Installation, Operation and Maintenance Manual P/N
26692
, or Appendix C.
Thread the Linear Actuator into the top of the SRM assembly.
Hand tighten only and ensure that
the brass hex portion of the Linear Actuator is fully bottomed against the SRM assembly
actuator assembly. Do not over tighten. Do not use PTFE thread tape.
LINEAR ACTUATOR
(P/N 24448)
THREAD LINEAR ACTUATOR
INTO ASSEMBLY UNTIL
FULLY BOTTOMED
P/N 26607 or
P/N 26577
FACTORY SUPPLIED PLUG. REMOVE
AND REPLACE WITH GAS TRIP
ASSEMBLY (P/N 12740) WHEN A
MECHANICAL GAS VALVE IS USED.
ENSURE SRM BODY (HEX) IS
FULLY BOTTOMED AGAINST
SRM BLOCK
Содержание 20150
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 12: ......
Страница 21: ......
Страница 43: ......
Страница 99: ......
Страница 101: ......
Страница 134: ......
Страница 140: ......
Страница 145: ......
Страница 156: ...December 2008 Section 7 Reset and Recharge Page 7 8 Amerex Restaurant Fire Suppression System EX 4658 ...
Страница 159: ......
Страница 171: ...APPENDIX C MANUAL P N 26692 AMEREX STRIKETM ECS INSTALLATION OPERATION MAINTENANCE MANUAL February 2019 ...