February 2019
Section 2 System Components
Page 2
-
4a
Amerex Restaurant Fire Suppression System
(EX 4658)
STRIKE™ RELEASING MODULE (SRM)
P/N: 26607: SRM with Stainless Steel Enclosure
The SRM is used in conjunction with the STRIKE™
ECS and is for UL Certification only and cannot be
considered for or used in installations of KP/ZD
systems in Canada.
The STRIKE™ Releasing Module is used to actuate the
agent cylinder discharge valve either automatically or
manually by puncturing a nitrogen cylinder.
Automatic and manual release of agent is accomplished
when the linear actuator receives a signal from the
STRIKE™ ECS Panel. This causes a spring loaded
plunger to perforate the rupture disc and releases
nitrogen thought the actuation hose/piping network to the
agent cylinder discharge valve(s).
Manual release of agent is accomplished in the same
manor by pulling on an electric manual pull station which
is connected to the STRIKE™ ECS Panel.
The SRM is designed for actuation networks with
more than two agent cylinders or in installations
using a mechanical gas valve.
Refer to page 3-29a
for limitations.
Operation of one or two mechanical gas valves may be accomplished by adding a Gas Trip
Assembly (P/N 12740). The cable for the gas valves may be attached to the SRM from ether of two
STRIKE™ RELEASING MODULE (SRM), OEM
P/N: 26577: SRM without Enclosure
The SRM, OEM lacks the stainless steel enclosure
and is used in hood end cabinet or OEM
installations.
1/4” NPT
OUTLET
FACTORY SUPPLIED PLUG. REMOVE
AND REPLACE WITH GAS TRIP
ASSEMBLY (P/N 12740) WHEN A
MECHANICAL GAS VALVE IS USED.
Содержание 20150
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 12: ......
Страница 21: ......
Страница 43: ......
Страница 99: ......
Страница 101: ......
Страница 134: ......
Страница 140: ......
Страница 145: ......
Страница 156: ...December 2008 Section 7 Reset and Recharge Page 7 8 Amerex Restaurant Fire Suppression System EX 4658 ...
Страница 159: ......
Страница 171: ...APPENDIX C MANUAL P N 26692 AMEREX STRIKETM ECS INSTALLATION OPERATION MAINTENANCE MANUAL February 2019 ...