December 2008
Section 3 ZD Design
Page 3 - 50
Amerex Restaurant Fire Suppression System
(EX 4658)
STAINLESS STEEL TUBING NOZZLE BRANCH LIMITATIONS:
All tubing and fittings leading from the supply branch tee to a dedicated appliance nozzle. One S.S. tubing
nozzle branch is allowed per cylinder. Example: If two cylinders are manifold together, then the use of two
S.S. tubing nozzle branches is permitted within that system.
MAX. FLOW
POINTS PER
BRANCH
PIPE SIZE
TOTAL
LINEAR FEET
OF PIPE
MAX. QTY.
TEES
MAX. QTY.
ELBOWS
2
3/8
10
1
6
NOTE
: 1. The tubing is to be 3/8” O.D. x 0.335” I.D. x 0.02 Thk. Wall annealed Stainless Steel Type 304.
2. The use of steel or stainless steel Bite-Seal compression fittings is required for use with
S.S. tubing.
3. No tube bending allowed.
GENERAL SYSTEM LIMITATIONS:
1.
Nozzle types may not be mixed on ZD nozzle branch lines.
2.
The discharge fitting, distributor and distribution hose are not to be included in any calculations.
3.
Duct nozzle has a
maximum vertical rise
above the supply branch line of
4'-0".
4.
Maximum cylinder centerline to cylinder centerline distance for manifold cylinders is to be 4 feet.
5.
The supply line has a
maximum vertical rise
above the distributor of
5 feet for the Model 375
Agent Cylinder and 10 feet for the Models 275 & 475 Agent Cylinders.
Содержание 20150
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 12: ......
Страница 21: ......
Страница 43: ......
Страница 99: ......
Страница 101: ......
Страница 134: ......
Страница 140: ......
Страница 145: ......
Страница 156: ...December 2008 Section 7 Reset and Recharge Page 7 8 Amerex Restaurant Fire Suppression System EX 4658 ...
Страница 159: ......
Страница 171: ...APPENDIX C MANUAL P N 26692 AMEREX STRIKETM ECS INSTALLATION OPERATION MAINTENANCE MANUAL February 2019 ...