February 2019
Section 1 General Information
Page 1 – 1
Amerex Restaurant Fire Suppression System (EX4658)
GENERAL INFORMATION
The Amerex KP / ZD Series Restaurant Wet Chemical Fire Suppression System is designed and has been
tested to provide fire protection for commercial cooking operations covering the hood, ducts, plenum and
appliances. Amerex Restaurant Fire Suppression Systems are a pre-engineered type as defined in NFPA
17A – Standard for Wet Chemical Extinguishing Systems. It is manufactured by the Amerex Corporation,
Trussville, Alabama.
It is essential that all installations of the Amerex KP / ZD Series Systems be performed in compliance with this
manual.
Those individuals responsible for the design, installation, operation and maintenance of
the Amerex Restaurant Fire Suppression System must be trained by Amerex and hold a current
Amerex Certificate.
All piping limitations, nozzle coverages, detector placements, etc. have been
proven and established through exhaustive testing by Underwriters Laboratories, Inc. Use of
components other than those referenced in this manual, or installations exceeding limitations stated in this
manual will void all of the Amerex KP / ZD Series System listings.
LISTINGS:
The Amerex KP / ZD Series Fire Suppression Systems are a listed pre-engineered fire extinguishing systems.
The KP & ZD systems are listed with Underwriters Laboratories, Inc. – USA per UL 300 fire test specification;
Underwriters Laboratories of Canada, Inc. per ULC/ORD 1254.6 – 1995 and Loss Prevention Certification
Board – UK per LPS 1223 rev. B.
The use of the STRIKE
TM
panel and SRM releasing device is not ULC
Certified.
Testing required for listings under these standards involve live fire tests under specific conditions
involving commercial kitchen hoods, ducts and appliances. Each test fire is allowed to reach its maximum
intensity before agent is discharged. Each test was repeated using both maximum and minimum piping,
variations in agent storage cylinder pressure to simulate maximum and minimum temperature
ratings. Duct fire tests were extinguished with fans off and fans on; dampers open and closed. Splash tests
for various appliances were conducted to assure that discharge of the agent would not cause excessive
splashing of hot grease to provide greater employee safety during commercial cooking operations.
UL Standard 300 introduces a series of tests by specifically addressing the use of high efficiency fryers,
ranges, woks and the unique fire extinguishing challenges that these appliances present.
DESIGN:
The Amerex KP Series Pre-Engineered Fire Suppression Systems consist of mechanical and electrical
components to be installed by an Authorized Factory Trained and Certified Amerex Restaurant Fire
Suppression Systems distributor. The system is composed of an Agent Cylinder/Discharge Valve charged
with Amerex Kitchen Wet Chemical Agent and a Mechanical Release Module (MRM or MRM II)
,
Pneumatic Release Module (PRM)
or a STRIKE
TM
panel / STRIKE
TM
Releasing Module (SRM)
. The
quantity of detectors, fusible links, nozzles, corner pulleys, pulley tees and manual pull stations will vary
depending on kitchen design.
The system operates either automatically if actuated by a detector or manually if actuated by a manual pull
station. Upon system operation, energy sources for the cooking appliances are required to be shut off
immediately. Electrical shutdown devices or suitable gas valves are referenced in this manual. Other
equipment such as audible/visual signaling devices can be added where required.
The Amerex Restaurant Fire Suppression System suppresses fire in commercial cooking equipment by
spraying Amerex Wet Chemical Agent in a pre-determined manner onto cooking appliances and into exhaust
ducts, filters and plenum areas. The primary means of fire suppression is either by saponification of surface
grease or by cooling the surface of oils and hot metal surfaces with fine droplets of agent, reducing the
temperature of the oil and appliance below the auto-ignition point.
Upon system discharge, the exhaust fans should be left on to aid in dispersal of the liquid suppressant that
results in cooling the plenum and duct. Any integral make-up or supply air should be automatically shut off
along with all cooking appliances. Some local Authorities Having Jurisdiction require exhaust fans to be shut
down by the fire suppression system. Check local fire codes, AHJ and Department of Health in the specific
area that the system is being installed for special installation requirements.
The Amerex Restaurant Fire Suppression System agent storage cylinders and cartridge shall not be installed
in environments below 32° F or above 120° F (0° C to 49° C).
Содержание 20150
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 12: ......
Страница 21: ......
Страница 43: ......
Страница 99: ......
Страница 101: ......
Страница 134: ......
Страница 140: ......
Страница 145: ......
Страница 156: ...December 2008 Section 7 Reset and Recharge Page 7 8 Amerex Restaurant Fire Suppression System EX 4658 ...
Страница 159: ......
Страница 171: ...APPENDIX C MANUAL P N 26692 AMEREX STRIKETM ECS INSTALLATION OPERATION MAINTENANCE MANUAL February 2019 ...