Mechanical Release Module
(w/10 In
3
cyl)
LIMITATIONS (SINGLE OR MULTIPLE AGENT CYLINDER ACTUATION NETWORK)
December 2008
Section 4 Installation
Page 4 – 15
Amerex Restaurant Fire Suppression System (EX 4658)
Nitrogen Cylinder
10 cu. in.
Maximum Total Length for:
Feet
Meters
¼" Copper Tubing
100
30.48
¼" ID Hose
54
16.45
¼" Schedule 40 Pipe
22.2
6.77
Copper Tubing
– ¼" O.D. Refrigeration Type (minimum
wall thickness of .049 inch). Use with brass or steel
compression style fittings (with brass or steel sleeves or
ferrules) or SAE 45° flared tube fittings. Maximum length
(including all fittings) – 100 Feet (30.48 m)
High Pressure Hose
– ¼" I.D. wire braid hose that is
factory supplied in 16” and 32” lengths.
Maximum length (including all fittings) –
54 feet (16.46 m) or a maximum of 40 hose assemblies
P/N 12854 or a maximum of 20 hose assemblies P/N
16448.
Pipe
– ¼" NPT Schedule 40 made of stainless steel,
chrome plated pipe or black iron pipe.
Maximum length – 22.2 feet (6.77 m)
Maximum tees – 9
Maximum elbows – 9
NOTE: 2 – 45° elbows = 1 – 90° elbow
NOTE:
Different methods of constructing the actuation
network may be mixed provided that the shortest
limitations are followed,
Example: A mix of ¼” copper tubing and ¼” high
pressure hose requires that the hose
limitations be followed (no more than 54 feet
[16.46m]) for the complete network. A mix
of ¼” high pressure hose and ¼” pipe
requires that the pipe limitations be followed
(no more than 22.2 feet [6.77m]) for the
complete work.
Possible location for
vent plug
Содержание 20150
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 12: ......
Страница 21: ......
Страница 43: ......
Страница 99: ......
Страница 101: ......
Страница 134: ......
Страница 140: ......
Страница 145: ......
Страница 156: ...December 2008 Section 7 Reset and Recharge Page 7 8 Amerex Restaurant Fire Suppression System EX 4658 ...
Страница 159: ......
Страница 171: ...APPENDIX C MANUAL P N 26692 AMEREX STRIKETM ECS INSTALLATION OPERATION MAINTENANCE MANUAL February 2019 ...