Inverter Settings
78
900-0117-01-00 Rev A
Figure 73
AC Input Current Limit
Set Points:
Input Type
: The inverter has two choices for incoming power;
Grid
or
Gen
. It is not capable of using
both at the same time. However, it can select between two different sources, typically the utility grid
and an AC generator, if properly switched. Each choice has parameters that define the usage of each
input. If
Input Type
is selected to
Grid
, the inverter uses the utility grid settings. (See page 79.) If the
menu is set to
Gen
, the inverter uses the generator settings. (See page 80.)
Note:
In OutBack grid-interactive inverters,
Input Type
also controls the cycle used by the inverter’s battery
charger. This overrides the selections offered in the
Charger Status
screen. (See page 51.)
~
Grid
selects a charge cycle consisting of bulk , absorption and float stages. Upon completion, the charger
goes into silent mode until it reaches the “re-float” voltage, when it will re-enter the float stage.
~
Gen
selects a
charge cycle consisting of bulk , absorption and float stages. Upon completion, the charger
remains in the float stage to maintain the batteries until the AC input is disconnected
.
The selection of the charge cycle does not automatically enable the charger. If the charger is disabled,
it must still be enabled using the t
he
Charger Status
screen. (See page 51.)
~
The
Input Type
selection also controls other AC source parameters, as described in the inverter
Operator’s Manual.
Note that if
Gen
is selected, a grid-interactive inverter will not sell power.
However, the AGS function (see page 114) will function even if
Grid
is selected.
Grid Input AC Limit:
Adjusts the inverter’s draw to the size of the utility grid circuit.
Gen Input AC Limit:
Adjusts the inverter’s draw to the size of the AC generator or generator circuit.
Charger AC Limit:
Adjusts the draw of the inverter’s charger. The maximum setting is equal to the
maximum delivery of the inverter’s charger. This setting can be limited to avoid accidentally
overcharging a small battery bank.
Input Support
: Enables the Input Support function, if present in the inverter. (If present, see the
inverter
Operator’s Manual
for information about this function.)
Содержание OutBack Power MATE3
Страница 1: ...MATE3 System Display and Controller Owner s Manual ...
Страница 22: ...Installation 20 900 0117 01 00 Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 142: ...Troubleshooting 140 900 0117 01 00 Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 144: ...Specifications 142 900 0117 01 00 Rev A NOTES ...
Страница 159: ......