Inverter Settings
88
900-0117-01-00 Rev A
Inverter Stacking
IMPORTANT:
All inverters connected to ports on the HUB must be assigned valid designations for stacking and Power
Save Levels. If this is not done, the system may give any number of Error messages or other symptoms.
This menu contains settings to coordinate, or “stack”, multiple inverters in a combined system. It also has
settings for Power Save Levels, which allow unused inverters to go into Silent mode to save power.
Stacking assigns an inverter to a particular phase or “leg”. Any inverter connected to an OutBack HUB
must be designated as master or slave of some type.
The available stacking configurations and menu options will vary with inverter model. Stacking
configurations, options, and other details are discussed in both the
Installation Manual
and the
Operator’s
Manual
for the inverter.
To access the
Inverter Stacking
menu:
1.
Access the
Inverter
menu as shown in Figure 71 on page 75.
2.
Use the control wheel to highlight the
Inverter Stacking
menu.
Press the button in the center of the control wheel to accept the selection.
3.
Use the control wheel to change the
Stack Mode
to the desired setting.
Press the button in the center of the control wheel to accept the selection.
This should automatically advance the highlighting to the
Master Power Save Level
set point.
4.
Use the control wheel to adjust the
Master Power Save Level
set point.
Press the button in the center of the control wheel to accept the selection.
This should automatically advance the highlighting to the
Slave Power Save Level
set point.
IMPORTANT:
Inverters with higher-level settings will go into Silent mode sooner. The master must
stay on and should have the lowest setting. The default is zero (0). Normally it should be
left at zero (0).
5.
Use the control wheel to adjust the
Slave Power Save Level
set point.
Press the button in the center of the control wheel to accept the selection.
6.
After setting the parameters for each set point, press the
TOP
navigation key to return to the
Main Menu
screen.
IMPORTANT:
Stack Modes are inverter-dependent. The Stack Modes listed show all possible Stack Modes,
some of which may not be available with all OutBack inverters.
The inverter’s
Installation Manual
describes the available stacking configurations for each
inverter and the modes required for each.
Do not select Stack Modes other than those identified for the specific inverter model being used.
Содержание OutBack Power MATE3
Страница 1: ...MATE3 System Display and Controller Owner s Manual ...
Страница 22: ...Installation 20 900 0117 01 00 Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 142: ...Troubleshooting 140 900 0117 01 00 Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 144: ...Specifications 142 900 0117 01 00 Rev A NOTES ...
Страница 159: ......