MATE3 Settings
120
900-0117-01-00 Rev A
AGS State-of-Charge (SOC) Start
With a FLEXnet DC, a generator can be started or stopped based on the battery state-of-charge (SOC)
rather than voltage. However, this feature may become less accurate if the system routinely cycles
without obtaining a full charge for long periods of time.
The
Enable Full Charge
set point overrides the
Stop SOC
function by establishing a time period from 1 to
30 days when the batteries will be charged to 100% regardless of the SOC value.
When the FLEXnet DC
days since parms met
exceeds this 1 to 30 day user-determined time,
the
Stop
SOC
is ignored. The generator will run until the FLEXnet DC’s charge parameters are met.
Setting this value to zero (0) days will disable the function. (No full charge will occur).
To enable the MATE3 to start the generator based on the battery SOC:
1.
Access the
MATE
menu as shown in Figure 113.
2.
Use the control wheel to select the
Advanced Generator Start
menu option.
Press the button in the center of the control wheel to accept the selection.
3.
Use the control wheel to highlight
State of Charge Start
.
Press the button in the center of the control wheel to select the menu item.
4.
Use the control wheel to select
N
for No (disabled) or
Y
for Yes (enabled).
5.
Press the
TOP
navigation key to return to the
Main Menu
screen.
Figure 119 MATE/AGS/State-of-Charge Start Screen
Set Points:
Enable
:
N
= No,
Y
= Yes
Start
SOC:
0 to 99%
Stop
SOC:
0 to 100%
Enable Full Charge:
N
= No,
Y
= Yes
Содержание OutBack Power MATE3
Страница 1: ...MATE3 System Display and Controller Owner s Manual ...
Страница 22: ...Installation 20 900 0117 01 00 Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 142: ...Troubleshooting 140 900 0117 01 00 Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 144: ...Specifications 142 900 0117 01 00 Rev A NOTES ...
Страница 159: ......