Battery Monitor Settings
900-0117-01-00 Rev A
109
Relay Mode
This menu allows the user to turn on or off an internal relay. The contacts of this relay are rated for 5 amps
at 30 Vdc. (This relay provides no voltage of its own.) The relay can be used as a switch to turn other
devices on or off. For more information on the battery monitor, see the
Relay Set Points
menu, and the
User’s Guide
for the FLEXnet DC.
To
access
the
Relay Mode
menu:
1.
Access the
Battery Monitor
menu as shown in Figure 106.
2.
Use the control wheel to highlight the
Relay Mode
menu.
Press the button in the center of the control wheel to accept the selection.
3.
Use the control wheel to increase or decrease the set points to the correct set point.
Press the button in the center of the control wheel to accept the selection.
This should automatically move the highlighting to the next set point.
4.
After setting the parameters for each set point, press the
TOP
navigation key to return to the
Main Menu
screen.
Figure 109 Relay Mode
Set Points:
Status
: The Relay output status is controlled by the <
Off
>,<
Auto
>
, and
<
On
>
soft keys.
~
<
On
> activates the relay immediately. Its contacts will remain continuously closed until Off is selected.
~
<
Auto
> sets the relay to be triggered by automatic criteria, according to the option selected in
Relay Set Points
.
~
<
Off
> disables the relay and prevents any of the
Relay Set Points
options from working. Note that even if
the relay output is set to
Off
, it may still be triggered by an external option not based in the battery monitor,
Invert Logic:
Switches the relay ‘s function from N.O. (a normally open state) to N.C. (a normally closed
state). The selections are
N
(no) and
Y
(yes). Since the default condition is N.O., the
N
selection means
it remains in this state. Selecting
Y
inverts the logic to N.C. The relay will close with an audible click
when this occurs.
Содержание OutBack Power MATE3
Страница 1: ...MATE3 System Display and Controller Owner s Manual ...
Страница 22: ...Installation 20 900 0117 01 00 Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 142: ...Troubleshooting 140 900 0117 01 00 Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 144: ...Specifications 142 900 0117 01 00 Rev A NOTES ...
Страница 159: ......