Operation
38
900-0117-01-00 Rev A
From the
Inverter
screen, the <
Next>
soft key brings up the Inverter Battery screen.
Figure 24
Inverter Battery Screen
Soft Keys:
<
Warn>
brings up a series of screens
with a list of non-critical inverter faults
and other information. These screens
are shown beginning on page 38.
<
Error>
brings up a screen with a list
of critical inverter faults. These screens
are shown beginning on page 39.
<
Back
> returns to the previous screen.
<
Port
> cycles through each device
connected to the network.
Inverter Screen
Inverter Battery Screen
Screen Items:
Actual
displays the uncompensated battery voltage.
Absorb
displays the Absorption voltage setting which was programmed into the inverter’s
charger. During the bulk and absorption stages, this is the target voltage used by the charger.
Float
displays the Float voltage setting which was programmed into the inverter’s charger.
During the float stage, this is the target voltage used by the charger.
Equalize
displays the Equalization voltage setting which was programmed into the inverter’s
charger. During the equalization charging cycle, this is the target voltage used by the charger.
Temp Comp
displays the corrected battery voltage after temperature readings are taken into
account from the Remote Temperature Sensor (RTS). If no RTS is present,
Temp Comp
and
Actual
will read the same.
Batt Temp
displays the battery temperature in degrees Celsius, as measured by the RTS. This
reading is only valid for port 1 on the HUB. If other ports are selected, or if no RTS is present, the
characters ### will be displayed.
Re-Float
displays the Re-Float setting which was programmed into the inverter’s charger. This is
the voltage used for the inverter to return from silent mode to the float stage.
Note:
If an arrow appears next to the items
Absorb
,
Float
, or
Equalize
, it indicates the charger is in that stage. The arrow will
not appear if the charger is in the bulk stage or silent mode.
Содержание OutBack Power MATE3
Страница 1: ...MATE3 System Display and Controller Owner s Manual ...
Страница 22: ...Installation 20 900 0117 01 00 Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 142: ...Troubleshooting 140 900 0117 01 00 Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 144: ...Specifications 142 900 0117 01 00 Rev A NOTES ...
Страница 159: ......