Charge Controller Settings
100
900-0117-01-00 Rev A
Auxiliary Output
This menu controls the output and functionality of the Auxiliary (AUX) output. The charge controller’s
AUX terminals provide a 12 Vdc output that can deliver up to 0.2 Adc to control external loads. Typical
loads include signaling a generator to start, sending a fault alarm signal, or running a small fan to cool the
inverter. See the charger controller
User’s Manual
for more information on hooking up the AUX terminals.
To
access
the
Auxiliary Output
menu:
1.
Access the
Charge Controller
menu as shown in Figure 90 on page 94.
2.
Use the control wheel to highlight the
Auxiliary Output
menu.
Press the button in the center of the control wheel to accept the selection.
3.
Use the control wheel to increase or decrease the set points to the correct voltage.
Press the button in the center of the control wheel to accept the selection.
This should automatically move the highlighting to the next set point.
4.
After setting the parameters for each set point, press the
TOP
navigation key to return to the
Main Menu
screen.
Figure 96
Auxiliary Output
Set Points:
Status
: The
Auxiliary Output
status is controlled by the <
Off
>, <
Auto
>, and <
On
> soft keys.
~
<On
>activates the
Auxiliary Output
immediately. It will display the message
Manual On
and
remain continuously active until <
Off
> is selected.
~
<Auto>
sets the
Auxiliary Output
to be triggered by automatic criteria, according to the option
selected in Aux Mode. When triggered, it displays the message
Auto On
; otherwise it displays
Auto Off
.
~
<Off>
disables the
Auxiliary Output
and prevents any of the charge controller’s automatic AUX
options from working. When <
Off>
is selected, it will display
Manual Off
. Note that even if the
AUX output is set to Off, it may still be triggered by an external option not based in the charge
controller, such as AGS. (See page 114.)
Aux Mode
: Selects one of nine options with automatic criteria. The options appear in the following
order when the wheel is drawn clockwise. The
Vent Fan
option appears first if the charge controller is
set at factory default values; otherwise, it will tend to display the last option selected. (The options are
described in greater detail in the charge controller
User’s Manual
.)
~
Vent Fan
enables the AUX output in response to high DC (battery) voltage. It can run a small fan
to ventilate the battery compartment to eliminate gases that result from battery charging.
Содержание OutBack Power MATE3
Страница 1: ...MATE3 System Display and Controller Owner s Manual ...
Страница 22: ...Installation 20 900 0117 01 00 Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 142: ...Troubleshooting 140 900 0117 01 00 Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 144: ...Specifications 142 900 0117 01 00 Rev A NOTES ...
Страница 159: ......