Inverter Settings
80
900-0117-01-00 Rev A
Gen AC Input Voltage Limits
The inverter will not connect to an AC source unless specific conditions are met. When
Input Type
is set to
Gen
in the
AC Input Current Limit
screen Figure 73 on page 78), this menu adjusts the limits on
acceptable voltage for a generator. (Frequency is not adjustable.) These limits will vary with the inverter
model. Check the
Operator’s Manual
for specific acceptance limits.
When the conditions list in this screen are met, the inverter will accept the generator after the designated
delay period (see below).
To access the
Gen AC Input Voltage Limits
menu:
5.
Access the
Inverter
menu as shown in Figure 71 on page 75.
6.
Use the control wheel to highlight the
Gen AC Input Voltage Limits
menu.
Press the button in the center of the control wheel to accept the selection.
7.
Use the control wheel to adjust the set point to the correct value.
Press the button in the center of the control wheel to accept the selection.
8.
Press the
TOP
navigation key to return to the
Main Menu
screen.
Figure 75
Gen AC Input Voltage Limit
Set Points:
Lower Voltage Limit:
Sets the low limit on the acceptable AC voltage. If the source is above this
voltage, the inverter will accept it. If it drops below this voltage, the inverter will return to inverting, if
enabled.
Upper Voltage Limit:
Sets the high limit on the acceptable AC voltage. If the source is below this
voltage, the inverter will accept it. If it rises above this voltage, the inverter will return to inverting, if
enabled.
Transfer Delay:
Sets the duration that the input AC voltage or frequency may exceed limits before the
inverter disconnects itself. This may be preceded by a warning (see page 39), and may be followed by
a
Last AC Disconnect
message (see page 54.)
Connect Delay:
Sets the designated delay period before the inverter begins accepting power from
the generator. This is intended to give the generator time to stabilize its output. It is not the same as
the warmup period used by the AGS function (see page 115.)
Содержание OutBack Power MATE3
Страница 1: ...MATE3 System Display and Controller Owner s Manual ...