Operation
900-0117-01-00 Rev A
23
Gen LED (green)
This LED is located on the
GEN
hot key. (See page 52) It provides a visual reference for the status of a
generator that is under control of the Advanced Generator Start (AGS) function. (See page 114.)
ON
– The generator is detected to be running after receiving an On command in the Generator Status
menu. The MATE3 determines the generator is running based on input AC voltage. This LED will
usually illuminate in conjunction with the
AC INPUT
LED.
OFF
(not illuminated) – The Generator Status menu has been set to Off, or the AGS function has not
been enabled. If the generator shuts down or stops delivering power, this LED will remain on until a
generator fault is declared.
Events LED (red)
This LED is located on the
EVENTS
hot key. (See page 53.) It provides a visual indication that an event
message has been generated. Events are usually indications of a warning or error condition.
ON
(solid) – An error has occurred. This is usually accompanied by inverter shutdown. This event can
also indicate a generator fault if the voltage is lost from an automatic generator. (See page 52.)
ON
(flashing) – A warning has occurred.
OFF
(not illuminated) – No event has occurred.
This LED will remain on until the event has been acknowledged in the
Event Status Detail
menu.
(See page 53.) It may be necessary to troubleshoot and deal with the cause of the event, using the
Inverter soft key. (See page 37 – 40.) Specific error or warning messages are defined in the inverter
Operator’s Manual
.
AC Input LED (yellow)
This LED is located on the
AC INPUT
hot key. (See page 54.) It provides a visual reference for the status
of the AC input.
ON
(solid): The AC source is connected and providing power. Unit may or may not be charging the
batteries, depending on settings.
ON
(flashing): The AC source is present but has not been accepted. If flashing continues, the unit is
refusing the source. This can occur for the following reasons.
~
The AC source may have quality issues. To determine system warnings for AC source problems see page 47
for the warnings menus. To view AC source measurements see page 54.
~
In the
AC INPUT
hot key menu, the
AC Input Status
is set to
Drop
~
The HBX function or the Grid Use Time function intentionally disconnected the inverter.
(See page 127 and page 129 for descriptions of these modes.)
OFF
(not illuminated): No AC source is detected.
If any inverters in a stacked system have a different inverting status from the master, this LED will not
display their status.
Содержание OutBack Power MATE3
Страница 1: ...MATE3 System Display and Controller Owner s Manual ...
Страница 22: ...Installation 20 900 0117 01 00 Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 142: ...Troubleshooting 140 900 0117 01 00 Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 144: ...Specifications 142 900 0117 01 00 Rev A NOTES ...
Страница 159: ......