MATE3 Settings
118
900-0117-01-00 Rev A
AGS Voltage Start
There are three voltage start set points in AGS mode that the user can select.
24 Hr Start
2 Hr Start
2 Minute Start
If the voltage drops below the voltage setting in these three menu items, a timer starts counting down.
When the timer reaches zero (0), a start command is sent to the generator. The
Quiet Time
settings
overrides the starting set points, preventing the generator from starting automatically. The exception is
2 Minute Start
, which is considered an “emergency” start set point and which will start the generator
regardless of
Quiet Time
settings.
After a generator is started due to a
Voltage Start
setting, it will be stopped when the inverter completes
the absorb charge or based on the
DC Genset
setting in the
AGS Setup
menu.
IMPORTANT:
If the DC Genset is set to YES, the generator will only stop after the battery voltage has
reached the
DC Genset
voltage for 15 minutes, or the
SOC Stop %
setting.
To Enable the AGS to start the generator based on battery voltage:
1.
Access the
MATE
menu as shown in Figure 113.
2.
Use the control wheel to select the
Advanced Generator Start
menu option.
Press the button in the center of the control wheel to accept the selection.
3.
Use the control wheel to highlight
Voltage Start
.
Press the button in the center of the control wheel to select the menu item.
4.
Use the control wheel to select
N
for no (disabled) or
Y
for yes (enabled) for each set point.
Press the button in the center of the control wheel to accept the selection.
This should advance the highlighting to the next set point.
5.
Press the
TOP
navigation key to return to the
Main Menu
screen.
Figure 117 MATE/AGS/Voltage Start Screen
Set Points:
24 Hr Start Enable
:
N
=No,
Y
=Yes
Voltage
xx.x (inverter dependent)
2 Hour Start Enable
:
N
=No,
Y
=Yes
Voltage
xx.x (inverter dependent)
2 Minute Start Enable
:
N
=No,
Y
=Yes
Voltage
xx.x (inverter dependent)
Содержание OutBack Power MATE3
Страница 1: ...MATE3 System Display and Controller Owner s Manual ...
Страница 22: ...Installation 20 900 0117 01 00 Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 142: ...Troubleshooting 140 900 0117 01 00 Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 144: ...Specifications 142 900 0117 01 00 Rev A NOTES ...
Страница 159: ......