Inverter Settings
900-0117-01-00 Rev A
85
Auxiliary Output
This menu controls the output and functionality of the Auxiliary (AUX) output. The inverter’s Auxiliary
(AUX) terminals provide a 12 Vdc output that can deliver up to 0.7 Adc to control external loads. Typical
loads include signaling a generator to start, sending a fault alarm signal, or running a small fan to cool the
inverter. See the inverter
Installation Manual
for more information on hooking up the AUX terminals. This
menu controls the output and functionality of the Auxiliary (AUX) output.
To access the
Auxiliary Output
menu:
1.
Use the control wheel to highlight the
Auxiliary Output
menu.
Press the button in the center of the control wheel to accept the selection.
2.
Use the control wheel to change the AUX mode to the desired setting.
Press the button in the center of the control wheel to accept the selection.
3.
Press either the <
Off
>, <
Auto
>, or <
On
> soft keys to change the status of the function.
4.
After setting the parameters for each set point, press the
TOP
navigation key to return to the
Main Menu
screen.
Figure 80
Auxiliary Output
Set Points:
Status
: The Auxiliary output status is controlled from by the <
Off
>,<
Auto
>, and <
On
> soft keys.
~
<
On
> activates the AUX output immediately. It will remain continuously active until Off is
selected. If this soft key is pressed, the screen will display
Manual On
.
~
<
Auto
> sets the AUX to be triggered by automatic criteria, according to the option selected in
Aux Mode. If this soft key is pressed, the screen will display
Auto On
or
Auto Off
.
~
<
Off
> disables the Auxiliary output and prevents any of the inverter’s automatic AUX options
from working. Note that even if the AUX output is set to Off, it may still be triggered by an
external option not based in the inverter, such as AGS. (See page 114.) If this soft key is pressed,
the screen will display
Manual Off
.
Aux Mode:
Selects one of nine options with automatic criteria. The options appear in the following
order when the wheel is drawn clockwise. (The options are described in greater detail in the inverter
Operator’s Manual
.)
Remote
,
Fault
,
Cool Fan
, and
AC Drop
have no adjustable settings. In Figure 80,
Cool Fan
is shown as an example of an option that has no adjustments.
~
Remote
allows the AUX output to be enabled in response to manual or automatic commands
based in the MATE3 (such as AGS). Although the MATE3 can control the AUX output even when
one of the other options is enabled,
Remote
keeps the inverter from interfering with the MATE3.
Содержание OutBack Power MATE3
Страница 1: ...MATE3 System Display and Controller Owner s Manual ...
Страница 22: ...Installation 20 900 0117 01 00 Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 142: ...Troubleshooting 140 900 0117 01 00 Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 144: ...Specifications 142 900 0117 01 00 Rev A NOTES ...
Страница 159: ......