Operation
46
900-0117-01-00 Rev A
Grid Soft Key
Figure 37
Grid Soft Key Screens
Figure 38
Sell Status Screen
Screen Items:
Selling Disabled:
The
Grid-Tie Enable
command
has been set to
N
(no). See page 88.
Qualifying Grid:
The inverter is running a timed
test during which it analyzes the grid quality. The
timer is shown on the screen. (If the inverter is
not a grid-interactive model, a random number
may be displayed.) The timer duration is listed in
the inverter
Operator’s Manual.
Frequency Too Low/Too High, Voltage Too
Low/Too High:
The frequency or voltage are
outside the acceptable limits for that model of
inverter. The
Operator’s Manual
lists that model’s
acceptable frequency and voltage range.
Battery <= xxxx:
The battery voltage is below
the target voltage for that stage (Float, SellRE,
etc). No excess energy is available to sell.
AC2 (gen) Selected:
The
Input Type
command
has been set to
Gen
. The inverter will not
knowingly sell to a generator. See page 76.
Soft Keys:
<
Back
> returns to the previous screen.
<
Port
> cycles through each device
connected to the network.
Grid Soft Key
Press this soft key to
view utility grid status
information.
Soft Keys:
<
Sell Status>
brings up a group of messages indicating
possible reasons for the inverter to fail to sell to the utility grid.
<
Back
> returns to the previous screen.
<
Port
> cycles through each device connected to the network.
Screen Items:
Grid
displays the current AC voltage from the
utility grid.
Min
displays the lowest recorded AC voltage
that day, and the time it was recorded.
Max
displays the highest recorded AC voltage
that day, and the time it was recorded.
Mode
displays the inverter’s current operating
status (either buying or selling) and the
number of kilowatts being bought or sold. This
status will be blank if grid power is not present.
Содержание OutBack Power MATE3
Страница 1: ...MATE3 System Display and Controller Owner s Manual ...
Страница 22: ...Installation 20 900 0117 01 00 Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 142: ...Troubleshooting 140 900 0117 01 00 Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 144: ...Specifications 142 900 0117 01 00 Rev A NOTES ...
Страница 159: ......