136
Rockwell Automation Publication 2097-UM002D-EN-P - April 2017
Appendix A
Interconnect Diagrams
Figure 63 - Kinetix 350 Drive with TL-Series™ (TLY-A) Motors
5
3
2
1
BR+
BR-
7
9
W
V
U
GND
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Green/Yellow
Blue
Black
Brown
Black
White
W
V
U
WHT/BLUE
GREEN
WHT/GREEN
GRAY
WHT/GRAY
BLACK
WHT/BLACK
RED
WHT/RED
1
2
3
4
5
10
14
6
12
YELLOW
WHT/YELLOW
13
8
AM+
AM-
BM+
BM-
IM+
IM-
+5VDC
ECOM
S1
S2
S3
SHIELD
22
23
15
24
17
19
9
10
11
12
13
14
5
3
2
1
BR+
BR-
7
9
W
V
U
GRAY
WHT/GRAY
22
23
14
6
24
GND
ORANGE
WHT/ORANGE
6
BAT+
BAT-
+5VDC
ECOM
SHIELD
BAT+
BAT-
DATA+
DATA-
GREEN
WHT/GREEN
13
14
5
10
CR1
MTR_BRAKE -
MTR
44
43
24V DC
24V DC COM
Motor Brake
Three-phase
Motor Power
Motor
Feedback
TLY-A
xxxx
-H (230V)
Servo Motors with
Incremental Feedback
2090-K2CK-D15M
Connector Kit
2090-CFBM6DF-CBAA
xx
(flying-lead) or
2090-CFBM6DD-CCAA
xx
(with drive-end connector)
Feedback Cable
Note 9
I/O (IOD)
Connector
Motor Power
(MP) Connector
2097-V3
x
PR
x
-LM
Kinetix 350 Drives
Motor Feedback
(MF) Connector
2090-CPBM6DF-16AA
xx
Motor Power and Brake Cable
Notes 9, 10
Use 2090-CPWM6DF-16AA
xx
cable for non-brake applications.
User Supplied
24V DC
See low-profile connector
illustration (lower left)
for proper grounding technique.
Turn clamp over to hold
small cables secure.
Exposed shield that is secured
under clamp.
Clamp Screws (2)
for note information.
TLY-A
xxxx
-B (230V)
Servo Motors with
High-Resolution Feedback
Cable Shield
Clamp
Only 3.6V battery (2090-DA-BAT2)
required for use with TLY-A
xxxx
-B motors
(high-resolution 17-bit encoders).
Clamp
2090-CFBM6DF-CBAA
xx
(flying-lead) or
2090-CFBM6DD-CCAA
xx
(with drive-end connector)
Feedback Cable
Note 9
See low-profile connector
illustration (lower left)
for proper grounding technique.
Low Profile Connector
(2090-K2CK-D15M shown)
Grounding Technique for
Feedback Cable Shield
Note 6
Содержание Kinetix 350
Страница 4: ...4 Rockwell Automation Publication 2097 UM002D EN P April2017 Summary of Changes Notes ...
Страница 50: ...50 Rockwell Automation Publication 2097 UM002D EN P April2017 Chapter 3 Kinetix 350 Drive Connector Data Notes ...
Страница 154: ...154 Rockwell Automation Publication 2097 UM002D EN P April2017 Appendix C Leakage Current Specifications Notes ...
Страница 159: ...Rockwell Automation Publication 2097 UM002D EN P April2017 159 Index Notes ...
Страница 160: ...160 Rockwell Automation Publication 2097 UM002D EN P April2017 Index ...
Страница 161: ......