106
Rockwell Automation Publication 2097-UM002D-EN-P - April 2017
Chapter 6
Kinetix 350 Drive Safe Torque-off Feature
Safe Torque-off Wiring Requirements
The following are the safe torque-off (STO) wiring requirements. The wire
must be copper with 75 °C (167 °F) minimum rating.
Figure 48 - Safe Torque-off (STO) Terminal Plug
IMPORTANT
The National Electrical Code and local electrical codes take precedence over
the values and methods provided.
IMPORTANT
Stranded wires must terminate with ferrules to prevent short circuits, per
table D7 of EN ISO 13849.
1 2 3 4 5 6
+24 V DC c
ontrol
Contr
ol COM
Safety
status
Safety
input 1
Safety
COM
Safety
input 2
Table 42 - Safe Torque-off (STO) Terminal Plug Wiring
Safe Torque-off (STO) Connector
Recommended Wire Size
Strip Length
mm (in.)
Torque Value
N•m (lb•in)
Pin
Signal
Stranded Wire
with Ferrule
mm² (AWG)
Solid Wire
mm²
(AWG)
STO-1
STO-2
STO-3
STO-4
STO-5
STO-6
+24V DC Control
Control COM
Safety Status
Safety Input 1
Safety COM
Safety Input 2
0.75 (18)
1.5 (16)
6 (0.25)
0.2 (1.8)
IMPORTANT
Use only pins STO-1 (+24V DC Control) and STO-2 (Control COM) of the
motion-allowed jumpers to defeat the safe torque-off function. When the
safe torque-off function is in operation, the 24V supply must come from an
external source.
IMPORTANT
To be sure of system performance, run wires and cables in the wireways as
established in the user manual for your drive.
Содержание Kinetix 350
Страница 4: ...4 Rockwell Automation Publication 2097 UM002D EN P April2017 Summary of Changes Notes ...
Страница 50: ...50 Rockwell Automation Publication 2097 UM002D EN P April2017 Chapter 3 Kinetix 350 Drive Connector Data Notes ...
Страница 154: ...154 Rockwell Automation Publication 2097 UM002D EN P April2017 Appendix C Leakage Current Specifications Notes ...
Страница 159: ...Rockwell Automation Publication 2097 UM002D EN P April2017 159 Index Notes ...
Страница 160: ...160 Rockwell Automation Publication 2097 UM002D EN P April2017 Index ...
Страница 161: ......