Rockwell Automation Publication 2097-UM002D-EN-P - April 2017
109
Kinetix 350 Drive Safe Torque-off Feature
Chapter 6
Figure 51 - Single-axis Relay Configuration (Stop Category 0) with Manual Reset
Safe Torque-off Signal
Specifications
This table provides specifications for the safe torque-off signals that are used in
the Kinetix 350 servo drives.
+24V DC
COM
Status
Safety Input 1
Safety Common
Safety Input 2
1
2
3
4
5
6
440R-D22R2
Input 1
DI
Input 2
A1
S11
S21
S12
S22
S32
S42
S34
13
23
A2
Y32
L12
L11
14
24
CR1
Reset
+
-
Kinetix 350 Drive
Safe Torque-off (STO)
Connector with
Wiring Header
External 24V COM
Safe Torque-off
Demand
Ex24V
Allen-Bradley
Monitoring Safety Relay
MSR127RP (440R-N23135)
Auxiliary Signal
to PLC
Pins 1 and 2 are not used when using Safety Inputs.
Pin 3 is a sinking output.
Attribute
Value
Safety inputs
(1)
(1) Safety inputs are not designed for pulse testing.
Insulated, compatible with single-ended output (+24V DC)
Enable voltage range: 20…24V DC
Disable voltage range: 0…1.0V DC
Input impedance
6.8 kΩ
Safety status
Isolated Open Collector (Emitter is grounded.)
Output load capability
100 mA
Digital outputs max voltage
30V DC
Содержание Kinetix 350
Страница 4: ...4 Rockwell Automation Publication 2097 UM002D EN P April2017 Summary of Changes Notes ...
Страница 50: ...50 Rockwell Automation Publication 2097 UM002D EN P April2017 Chapter 3 Kinetix 350 Drive Connector Data Notes ...
Страница 154: ...154 Rockwell Automation Publication 2097 UM002D EN P April2017 Appendix C Leakage Current Specifications Notes ...
Страница 159: ...Rockwell Automation Publication 2097 UM002D EN P April2017 159 Index Notes ...
Страница 160: ...160 Rockwell Automation Publication 2097 UM002D EN P April2017 Index ...
Страница 161: ......