Rockwell Automation Publication 2097-UM002D-EN-P - April 2017
123
Troubleshoot the Kinetix 350 Drive
Chapter 7
Abnormal noise
Motor tuning limits are set too high.
Run Tune in RSLogix 5000 software.
Loose parts are present in the motor.
• Remove the loose parts.
• Return motor for repair.
• Replace motor.
Through bolts or coupling is loose.
Tighten bolts.
The bearings are worn.
Return motor for repair.
Mechanical resonance.
Notch filter can be required (refer to Axis Properties
dialog box, Output tab in RSLogix 5000 software).
Erratic operation - Motor
locks into position, runs
without control or with
reduced torque.
Motor power phases U and V, U and W, or V and W reversed.
Check and correct motor power wiring.
Sine, cosine, or rotor leads are reversed in the feedback cable connector.
Check and correct motor feedback wiring.
Sine, cosine, rotor lead sets of resolver feedback are reversed.
Check and correct motor feedback wiring.
No motion from a motor with a TTL
encoder, axis is enabled and there
are no faults
Sine and cosine signals are broken.
Check feedback wiring.
Table 56 - General System Behavior (Continued)
Condition
Potential Cause
Possible Resolution
Содержание Kinetix 350
Страница 4: ...4 Rockwell Automation Publication 2097 UM002D EN P April2017 Summary of Changes Notes ...
Страница 50: ...50 Rockwell Automation Publication 2097 UM002D EN P April2017 Chapter 3 Kinetix 350 Drive Connector Data Notes ...
Страница 154: ...154 Rockwell Automation Publication 2097 UM002D EN P April2017 Appendix C Leakage Current Specifications Notes ...
Страница 159: ...Rockwell Automation Publication 2097 UM002D EN P April2017 159 Index Notes ...
Страница 160: ...160 Rockwell Automation Publication 2097 UM002D EN P April2017 Index ...
Страница 161: ......