112
Rockwell Automation Publication 2097-UM002D-EN-P - April 2017
Chapter 7
Troubleshoot the Kinetix 350 Drive
Interpret Status Indicators
See these troubleshooting tables to identify faults, potential causes, and the
appropriate actions to resolve the fault. If the fault persists after attempting to
troubleshoot the system, please contact your Rockwell Automation sales
representative for further assistance.
Four-digit Display Messages
The control modules include a four-digit seven-segment display for status and
fault messages. The display scrolls to display text strings.
The Four-digit Display Messages table lists the messages along with their
priorities. When messages of different priorities are to be displayed, for
example, when the drive has both a fault and a start inhibit, only the higher
priority message is displayed. When messages of equal priority are needed, for
example, when there is multiple fault, the messages are displayed in a round-
robin fashion. Only two messages scroll in this manner. When a fault is
annunciated, the entire fault text scrolls on the display regardless of when the
fault is cleared
The IP address is always an active condition, meaning that it scrolls with the
axis state as long as there are no higher priority messages to display.
See the table on
for a description of the messages
that scroll across the display during powerup.
Table 43 - Four-digit Display Messages
Device Condition
Display Digit
Priority
(Lower Is
Higher)
IP address (always active)
xxx.xxx.xxx.xxx
4
Executing device self-test
-08-
Waiting for connection to controller
-00-
Configuring device attributes
-01-
Waiting for group synchronization
-02-
Waiting for DC Bus to charge
-03-
Device is operational
-04-
Start inhibit code
S
xx
3
Start inhibit code - custom
Sc
xx
Axis fault code
F
xx
2
Axis fault code - custom
Fc
xx
Boot error
L
xxx
1
Power on Self Test (POST) error
P
xxx
Initialization fault code - custom
Ic
xx
Node fault code
nF
xx
1
Содержание Kinetix 350
Страница 4: ...4 Rockwell Automation Publication 2097 UM002D EN P April2017 Summary of Changes Notes ...
Страница 50: ...50 Rockwell Automation Publication 2097 UM002D EN P April2017 Chapter 3 Kinetix 350 Drive Connector Data Notes ...
Страница 154: ...154 Rockwell Automation Publication 2097 UM002D EN P April2017 Appendix C Leakage Current Specifications Notes ...
Страница 159: ...Rockwell Automation Publication 2097 UM002D EN P April2017 159 Index Notes ...
Страница 160: ...160 Rockwell Automation Publication 2097 UM002D EN P April2017 Index ...
Страница 161: ......