130
Rockwell Automation Publication 2097-UM002D-EN-P - April 2017
Appendix A
Interconnect Diagrams
Interconnect Diagram Notes
This appendix provides wiring examples to assist you in wiring the Kinetix® 350
system. These notes apply to the wiring examples on the pages that follow.
Note
Information
1
For power wiring specifications, refer to
2
For input fuse and circuit breaker sizes, refer to on
3
Place the AC (EMC) line filters as close to the drive as possible and do not route very dirty wires in the wireway. If routing in wireway is unavoidable, use shielded cable
with shields that are grounded to the drive chassis and filter case. For AC line filter specifications, refer to Kinetix 350 Drive Power Specifications in Kinetix Servo Drives
Specifications Technical Data, publication
.This filter does not apply to 2097-V32PR
x
-LM drives because they have integrated AC line filters.
4
Terminal block is required to make connections.
5
Contactor coil (M1) needs integrated surge suppressors for AC coil operation. See on
6
See the Motor Brake Currents table on
to size the interposing relay for your application and for a detailed schematic of brake implementation.
7
Drive Enable input must be opened when main power is removed, or a drive fault occurs. A delay of at least 1.0 second must be observed before attempting to enable the
drive after main power is restored.
8
Cable shield clamp must be used to meet CE requirements. No external connection to ground is required.
9
For motor cable specifications, refer to the Kinetix Motion Accessories Specifications Technical Data, publication
10
Motor power cables (catalog numbers 2090-XXNPMF-
xx
S
xx
and 2090-CPBM6DF-16AA
xx
) have a drain wire that must be folded back under the cable shield clamp.
11
MPL-A
xxx
and MPL-B15
xxx
-H...MPL-B45
xxx
-H, MPM-A
xxx
, MPF-A
xxx,
MPS-A
xxx
, MPAR-A
xxx
, MPAI-A
xxx
, and MPAS-A
xxx
, encoders use the +5V DC supply.
12
MPL-B15
xxx-
S/M...MPL-B45
xxx
-S/M, MPM-B
xxx
, MPF-B
xxx,
MPS-B
xxx
, MPAR-B
xxx
, MPAI-B
xxx
, and MPAS-B
xxx
,
encoders use +9V DC.
13
Brake connector pins are labeled plus (+) and minus (-) or F and G respectively. Power connector pins are labeled U, V, W, and GND or
A, B, C, and D respectively.
Содержание Kinetix 350
Страница 4: ...4 Rockwell Automation Publication 2097 UM002D EN P April2017 Summary of Changes Notes ...
Страница 50: ...50 Rockwell Automation Publication 2097 UM002D EN P April2017 Chapter 3 Kinetix 350 Drive Connector Data Notes ...
Страница 154: ...154 Rockwell Automation Publication 2097 UM002D EN P April2017 Appendix C Leakage Current Specifications Notes ...
Страница 159: ...Rockwell Automation Publication 2097 UM002D EN P April2017 159 Index Notes ...
Страница 160: ...160 Rockwell Automation Publication 2097 UM002D EN P April2017 Index ...
Страница 161: ......