Rockwell Automation Publication 1444-UM001D-EN-P - June 2018
75
Install the Dynamix 1444 Series Monitoring System
Chapter 2
EtherNet/IP Connector
Typically, Ethernet network connections are made with pre-assembled
(standard) patch cords to interconnect modules according to the desired
network topology.
Each module has an integrated switch and two functionally equal (Port 1 and
Port 2) RJ45 connectors.
The total length of Ethernet cable connecting main-to- main, main-to-
controller, or main-to-switch must not exceed 100 m (328 ft.).
If the entire channel is constructed of stranded cable (no fixed cable), then
calculate maximum length as follows:
Maximum Length = (113-2N)/y, meters
Where:
• N = the number of connections in the channel
• y = the loss factor that is compared to fixed cable (typically 1.2…1.5)
Wire the RJ45 connector as shown.
IMPORTANT
See Ethernet Cables, channel class and category and recommended cables
under “
Cable, Connector, and Mounting Accessories on page 17
,” for
additional information on Ethernet connectivity.
8
NC
7
NC
6
RD-
5
NC
4
NC
3
RD+
2
TD
1
TD+
Содержание 1444-AOFX00-04RB
Страница 10: ...10 Rockwell Automation Publication 1444 UM001D EN P June 2018 Table of Contents Notes...
Страница 12: ...12 Rockwell Automation Publication 1444 UM001D EN P June 2018 Preface Notes...
Страница 198: ...198 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 5 Configure the Tachometer Expansion Module Notes...
Страница 210: ...210 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 7 Configure Relays Notes...
Страница 230: ...230 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 8 Configure Alarms Notes...
Страница 240: ...240 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 9 Trend and Transient Capture Notes...
Страница 316: ...316 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 10 Operate the Module Notes...
Страница 549: ......