524
Rockwell Automation Publication 1444-UM001D-EN-P - June 2018
Appendix A
CIP Objects
Table 279 - Analog Output Module / Tacho Signal Conditioner Status
Bit
Description (Analog Output Module)
Bit
Description (Tacho Signal Conditioner)
0
Analog output module not responding. If set
disregard other bits in this group.
16
Tacho signal conditioner module not
responding. If set disregard other bits in this
group.
1
Module is configured (so normally expected
set).
17
Module is configured (so normally expected
set).
2
Code CRC fault.
18
Code CRC fault.
3
High temperature warning.
19
High temperature warning.
4
Link/bus fail.
20
Link/bus fail.
5
Halt is active.
21
Halt is active.
6
RAM fault.
22
RAM fault.
7
RAM access error.
23
RAM access error.
8
Channel 0 not inhibited (so normally set).
24
Spare
9
Channel 1 not inhibited.
25
10
Channel 2 not inhibited.
26
Speed 0 Estimated.
11
Channel 3 not inhibited.
27
Speed 1 Estimated.
12
Spare
28
+25V5 supply fail.
13
29
-25V5 supply fail.
14
30
Tacho 0 sensor fault.
15
31
Tacho 1 sensor fault.
Содержание 1444-AOFX00-04RB
Страница 10: ...10 Rockwell Automation Publication 1444 UM001D EN P June 2018 Table of Contents Notes...
Страница 12: ...12 Rockwell Automation Publication 1444 UM001D EN P June 2018 Preface Notes...
Страница 198: ...198 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 5 Configure the Tachometer Expansion Module Notes...
Страница 210: ...210 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 7 Configure Relays Notes...
Страница 230: ...230 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 8 Configure Alarms Notes...
Страница 240: ...240 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 9 Trend and Transient Capture Notes...
Страница 316: ...316 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 10 Operate the Module Notes...
Страница 549: ......