Rockwell Automation Publication 1444-UM001D-EN-P - June 2018
181
Measurement Definition
Chapter 4
Output
The Complementary Differential Expansion measurement, in mils (mm), or
other EU, is output to the associated tag as shown in
. The individual
channel DC volt values are provided in their respective tags.
Figure 75 - Differential Expansion Tag (Channels 2 and 3)
illustrates the tag that is created for a channel 2/3 measurement. If a
channel 0/1 measurement is defined, the tag is
“Ch0_1DifferentialExpansion”.
also shows the Bias/Gap tags for the
channels, which have been added on the Inputs page, for the Differential
Expansion channel pair.
Ramp Differential Expansion Measurements
Ramp/Differential Expansion is used when one or both of the sensors are
installed such that they monitor the movement of an angled surface, or “ramp”.
This method can be applied using either of three orientations, as illustrated in
Figure 76 - Ramp Differential Expansion Probe Arrangements
Содержание 1444-AOFX00-04RB
Страница 10: ...10 Rockwell Automation Publication 1444 UM001D EN P June 2018 Table of Contents Notes...
Страница 12: ...12 Rockwell Automation Publication 1444 UM001D EN P June 2018 Preface Notes...
Страница 198: ...198 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 5 Configure the Tachometer Expansion Module Notes...
Страница 210: ...210 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 7 Configure Relays Notes...
Страница 230: ...230 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 8 Configure Alarms Notes...
Страница 240: ...240 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 9 Trend and Transient Capture Notes...
Страница 316: ...316 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 10 Operate the Module Notes...
Страница 549: ......