Chapter 8
Configure Alarms
If an Input that is included in the specific Logic references a Measurement
Alarm that is not enabled, then an error symbol is presented next to the Input,
along with a notice following the Measurement Alarms selections. See
Figure 90 - Measurement Alarms
Inputs
There are two elements to the inputs of a voted alarm including the
measurement alarm status and a list of measurement alarms. The status
definition provides the specific conditions that this voted alarm acts on; alert
and/or danger and/or transducer fault. The other input is a list of up to four
enabled measurement alarms to use as input to the voting logic. (For example, 1
out of 2, 3 out of 4).
Logic
Logic is the “A out of B” voting that is applied to the inputs. Selections are
provided which support various combinations of four inputs and include:
For the AND and/or combinations, the inputs are grouped in the order they
are entered. That is, inputs 0 and 1 for the BEFORE the and/or statement logic
and inputs 2 and 3 for the AFTER the and/or statement logic.
For a vote to resolve to TRUE (1), the logic must be satisfied with inputs that
are all in the same condition, and as defined for the voted alarm (alert/danger/
fault).
Logic
1 Out Of 1
1 Out Of 4
1 Out Of 2
2 Out Of 4
2 Out Of 2
3 Out Of 4
1 Out Of 3
4 Out Of 4
2 Out Of 3
1 Out Of 2 AND 1 Out Of 2
3 Out Of 3
2 Out Of 2 OR 2 Out Of 2
1 Out Of 2 AND 2 Out Of 2
2 Out Of 2 AND 1 Out Of 2
Содержание 1444-AOFX00-04RB
Страница 10: ...10 Rockwell Automation Publication 1444 UM001D EN P June 2018 Table of Contents Notes...
Страница 12: ...12 Rockwell Automation Publication 1444 UM001D EN P June 2018 Preface Notes...
Страница 198: ...198 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 5 Configure the Tachometer Expansion Module Notes...
Страница 210: ...210 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 7 Configure Relays Notes...
Страница 230: ...230 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 8 Configure Alarms Notes...
Страница 240: ...240 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 9 Trend and Transient Capture Notes...
Страница 316: ...316 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 10 Operate the Module Notes...
Страница 549: ......