Install the Dynamix 1444 Series Monitoring System
Chapter 2
In applications where the buffered outputs are infrequently used, a switch can
be installed between pins 57 and 58. When installed, open the switch to enable
the buffered outputs, and close the switch to disable the outputs.
It is possible to use a common switch to manage the buffered outputs of
multiple modules as the override pins are opto-isolated from the module
circuitry. When a common switch is required, wire one contact to pin 57 of the
module nearest the switch and the other to pin 58 of each module to be
managed.
Figure 12 - Wiring Buffer Outputs Override
Consider the following with the module:
• When you connect pin 58 from multiple modules to pin 57 on one
module, allow for a maximum 3 mA current sink for each connected
override input.
Temperature Considerations on page 30
for further information.
Содержание 1444-AOFX00-04RB
Страница 10: ...10 Rockwell Automation Publication 1444 UM001D EN P June 2018 Table of Contents Notes...
Страница 12: ...12 Rockwell Automation Publication 1444 UM001D EN P June 2018 Preface Notes...
Страница 198: ...198 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 5 Configure the Tachometer Expansion Module Notes...
Страница 210: ...210 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 7 Configure Relays Notes...
Страница 230: ...230 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 8 Configure Alarms Notes...
Страница 240: ...240 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 9 Trend and Transient Capture Notes...
Страница 316: ...316 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 10 Operate the Module Notes...
Страница 549: ......