302
Rockwell Automation Publication 1444-UM001D-EN-P - June 2018
Chapter 10
Operate the Module
Measurement Accuracy
Consider the following items relative to measurement accuracy:
• Absolute Error
Absolute error quantifies the average of the measurements that are
compared to the expected result. The measurement error, for both AC
and DC measurements, is less than ± 0.5%.
• Measurement Output Variation
Output variation describes how individual measurements of the same
input deviate from the average. For a given configuration, the modules
output variation is related to the signal amplitude. Small AC signals
experience the highest percentage deviations, example: 0.7% for signals
less than 100 mV p2p typically reducing to 0.2% or less for AC signals of
several volts and all DC measurements.
• Overall Accuracy
Overall measurement accuracy is the combination of the absolute
measurement error and measurement deviation, so it varies depending
on actual signal levels. Nevertheless, it is reasonable to expect a typical
overall measurement accuracy of not less than ± 1.0% of the typical
range or alarm limit.
Содержание 1444-AOFX00-04RB
Страница 10: ...10 Rockwell Automation Publication 1444 UM001D EN P June 2018 Table of Contents Notes...
Страница 12: ...12 Rockwell Automation Publication 1444 UM001D EN P June 2018 Preface Notes...
Страница 198: ...198 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 5 Configure the Tachometer Expansion Module Notes...
Страница 210: ...210 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 7 Configure Relays Notes...
Страница 230: ...230 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 8 Configure Alarms Notes...
Страница 240: ...240 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 9 Trend and Transient Capture Notes...
Страница 316: ...316 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 10 Operate the Module Notes...
Страница 549: ......