Chapter 10
Operate the Module
Figure 94 - Alarm Status
When selecting the appropriate alignment method, consider the following:
Static Alignment:
• Each voted alarm can have only one enabled output: Alert, Danger, or
Transducer Fault.
• Alarm Statuses align one-to-one with the corresponding Voted Alarm:
– Voted Alarm 0 -- > Alarm Status 0
– Voted Alarm 1 -- > Alarm Status 1
…
– Voted Alarm 12 -- > Alarm Status 12
• Relays are associated with an Alarm Status only if it references a Voted
Alarm.
• Relays that are configured to actuate on Fault (only) do not have an
associated Alarm Status.