276
Rockwell Automation Publication 1444-UM001D-EN-P - June 2018
Chapter 10
Operate the Module
Table 59 - Expansion Module Response Codes
Table 60 - 4…20 mA Module Status
Table 61 - Tachometer Signal Conditioner Module Status
Tag Description
ExpRelay0FaultCode
Relay Module 0 Fault Code
3-bit integer with values as follows:
ExpRelay1FaultCode
Relay Module 0 Fault Code
ExpRelay2FaultCode
Relay Module 0 Fault Code
ExpAnalogFaultCode
Analog Output Module Fault Code
ExpTachFaultCode
Tachometer Signal Conditioner
Module Fault Code
Value
Description
0
Normal / no exception
1
Invalid command / command not recognized
2
Reserved
3
Message and message content do not agree
4
Reserved
5
No message data received
6
Module is not configured
Tag
Description (if = 1)
ExpAnalogStatus
Analog Output Module Status
Container value allows access to hidden tags. The hidden tags provide no user actionable information. They are
provided to assist device diagnostics only.
See the
(class code 0x04), on page
, for the assembly members and bit assignments.
ExpAnalogOverTemperature
Analog Output Module Over Temperature Warning
Indicates when the processor board temperature is less than -20 °C (-4 °F) or greater than 70 °C (158 °F). While the
module rating is based on surrounding air temperature, depending on airflow, the board temperature can exceed the
surrounding air temperature by up to 25 °C (77 °F). This difference means that it is possible that the alarm limit could
be exceeded when the surrounding air temperature is as low as 45 °C (113 °F). Consequently, the indication is
considered only a warning.
ExpAnalogCh0Enabled
Analog Output Module Channel 0 Enabled
4…20mA output channel is enabled.
ExpAnalogCh1Enabled
Analog Output Module Channel 1 Enabled
ExpAnalogCh2Enabled
Analog Output Module Channel 2 Enabled
ExpAnalogCh3Enabled
Analog Output Module Channel 3 Enabled
Tag
Description (if = 1)
ExpTachStatus
Tachometer Signal Conditioner Module Status
Container value allows access to hidden tags. The hidden tags provide no user actionable information.
They are provided to assist device diagnostics only.
See the
, for the assembly members and bit
assignments.
ExpTachOverTemperature
Tachometer Signal Conditioner Module Over Temperature Warning
Indicates when the processor board temperature is less than -20 °C (-4 °F) or greater than 70 °C (158 °F).
While the module rating is based on surrounding air temperature, depending on airflow, the board
temperature can exceed the surrounding air temperature by up to 25 °C (77 °F). This difference means
that it is possible that the alarm limit could be exceeded when the surrounding air temperature is as low
as 45 °C (113 °F). Consequently, the indication is considered only a warning.
Содержание 1444-AOFX00-04RB
Страница 10: ...10 Rockwell Automation Publication 1444 UM001D EN P June 2018 Table of Contents Notes...
Страница 12: ...12 Rockwell Automation Publication 1444 UM001D EN P June 2018 Preface Notes...
Страница 198: ...198 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 5 Configure the Tachometer Expansion Module Notes...
Страница 210: ...210 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 7 Configure Relays Notes...
Страница 230: ...230 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 8 Configure Alarms Notes...
Страница 240: ...240 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 9 Trend and Transient Capture Notes...
Страница 316: ...316 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 10 Operate the Module Notes...
Страница 549: ......