Rockwell Automation Publication 1444-UM001D-EN-P - June 2018
247
Operate the Module
Chapter 10
If a reset is required, see
Resetting the Module on page 241
module is inhibited and does not have any established connections.
2. Update the firmware using ControlFLASH.
• An established class 1 connection must be normally closed. To close
the connection, you inhibit the module by executing a normal
shutdown of the controller, or cycle power on the module.
• After updating the module, verify that the module firmware has been
successfully updated.
While ControlFLASH reports the new version, the version reported
is only that of the auxiliary processor. However, the module has two
processors; an auxiliary processor and a Digital Signal Processor
(DSP), which also has firmware.
Firmware revisions are shown in
. The firmware
revision of both processors, and of any connected expansion
modules, can be viewed from the AOP Status page.
Figure 92 - Module Firmware
Firmware Update Error Handling on page 248
for information on how
errors in firmware updates are handled.
IMPORTANT
The Status page is only updated when the AOP is in RUN mode.
Содержание 1444-AOFX00-04RB
Страница 10: ...10 Rockwell Automation Publication 1444 UM001D EN P June 2018 Table of Contents Notes...
Страница 12: ...12 Rockwell Automation Publication 1444 UM001D EN P June 2018 Preface Notes...
Страница 198: ...198 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 5 Configure the Tachometer Expansion Module Notes...
Страница 210: ...210 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 7 Configure Relays Notes...
Страница 230: ...230 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 8 Configure Alarms Notes...
Страница 240: ...240 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 9 Trend and Transient Capture Notes...
Страница 316: ...316 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 10 Operate the Module Notes...
Страница 549: ......