Rockwell Automation Publication 1444-UM001D-EN-P - June 2018
147
Measurement Definition
Chapter 4
Measurement
Units
Select from:
• inch/s
• m/s
• mm/s
Select the engineering units for the TWF and FFT.
The rules for units selection, which are based on the transducer units (see the HW Configuration properties page),
are provided in this table.
For any acceleration, velocity or displacement (length) units, the module can convert the measurement between
equivalent Metric and English units.
Speed Reference
Select from:
• Speed 0
• Speed 1
• Factored Speed 0
• Factored Speed 1
Select the reference speed source.
When TWFs and FFTs are read from the module, the value of this RPM is included with the data.
Number of
Averages
Select from:
• 1
• 2
• 3
• 6
• 12
• 23
• 45
• 89
• 178
Select the number of averages for the FFT or TWF (see Average TWF later in this topic).
• If you select Average TWF, the module performs in the average time domain (available when you define the
measurement to use synchronous sampling). Otherwise the module performs with an average on the linear
FFT data.
• When averaging, the module updates the individual TWFs (and FFTs) as quickly as possible. How fast updating
occurs depends on the overall processing demands on the module, which is a function of the module
configuration and the current load. This factor, along with the fact that the module always captures TWFs with
maximum overlap, makes it impossible to define precisely how long (in time) it takes for the module to
acquire any specific number of samples to use in the averaging.
• Averaging is exponential. Once the module has acquired the specified number of samples, then the averaged
sample (result) is available after each subsequent update.
Average TWF
Enable (checked) / Disabled (not
checked)
Select the checkbox to perform the averaging in the time domain (on the TWFs). The module can average time
waveforms only if they are synchronously sampled. Set the Signal Source to Alternate Path, and set the Alternate
Path Processing Mode to Synchronous.
Clear the checkbox to average the FFTs instead of the TWFs.
Table 30 - FFT (continued)
Parameter
Values
Comment
CLASS
CHANGE EU OPTION
Temperature
Bearing Defect Units
No change allowed
Pressure
Flow
Current
Frequency
Power
Voltage
Acceleration
Velocity
Length
Change in class only
Displacement
Velocity
Acceleration
m
m/s
m/s
2
mm
mm/s
mm/s
2
micron
│
inch/s
│
inch/s
2
inch
g
mil
mg
Содержание 1444-AOFX00-04RB
Страница 10: ...10 Rockwell Automation Publication 1444 UM001D EN P June 2018 Table of Contents Notes...
Страница 12: ...12 Rockwell Automation Publication 1444 UM001D EN P June 2018 Preface Notes...
Страница 198: ...198 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 5 Configure the Tachometer Expansion Module Notes...
Страница 210: ...210 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 7 Configure Relays Notes...
Страница 230: ...230 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 8 Configure Alarms Notes...
Страница 240: ...240 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 9 Trend and Transient Capture Notes...
Страница 316: ...316 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 10 Operate the Module Notes...
Страница 549: ......