74
Rockwell Automation Publication 1444-UM001D-EN-P - June 2018
Chapter 2
Install the Dynamix 1444 Series Monitoring System
Connecting Speed Signals across Modules
When an external signal is used to serve multiple DYN modules, the
recommended wiring solution is as follows.
1. Wire the source signal to the TTL inputs on the first module, per
.
2. On the first module, wire one of its outputs to the TTL inputs. (#1) on
Opto-isolated (Open Collector) Outputs on
Example of wiring Discrete Output 0 to Tacho Input 0
Example of wiring Discrete Output 1 to Tacho Input 1
3. Daisy chain additional modules by repeating
and
.
4. To output the TTL signal the wired opto-isolated output must be
configured to replicate the “Local TTL Tach 0 Input” or “Local TTL
Tach 1 Input”, as appropriate. See
Hardware Configuration Page on
Use this method to daisy chain the external TTL signal to be sure that there is
isolation between modules. See
Speed Signal Replication on page 58
for more
information.
Содержание 1444-AOFX00-04RB
Страница 10: ...10 Rockwell Automation Publication 1444 UM001D EN P June 2018 Table of Contents Notes...
Страница 12: ...12 Rockwell Automation Publication 1444 UM001D EN P June 2018 Preface Notes...
Страница 198: ...198 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 5 Configure the Tachometer Expansion Module Notes...
Страница 210: ...210 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 7 Configure Relays Notes...
Страница 230: ...230 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 8 Configure Alarms Notes...
Страница 240: ...240 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 9 Trend and Transient Capture Notes...
Страница 316: ...316 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 10 Operate the Module Notes...
Страница 549: ......