For multiplexed measurements it is possible that the available Tacho Times do
not always provide full coverage for the sample data. This situation can occur
when low frequency / slow speed measurements, where fewer than 16 samples
per revolution and
the full extent of the circular sample buffers is used. This
can lead to errors in the speed measurement.
Individual mode is also implemented, where each channel is allocated to its
own individual time slot. As individual mode provides little operational
advantage over paired mode, the latter is recommended for all multiplexing
applications.
Dynamix Relay
Module Object
The Relay Module Object (class code 0x39C) configures the relay outputs of
the associated relay expansion modules (1…3 units per host, each serving four
mechanical relays).
The object defines the setup for the Relay Output expansion modules and the
interaction of these expansion modules with the main module. The same host
module can accommodate up to three Relay Output modules. There is an
object instance per module.
When one or more Relay modules are included in a system, not only must the
configuration aspects of this object be addressed, but the presence of each
module must also be flagged by appropriate setting of the Module Control
Object, class attribute 16 (Configured Auxiliary Modules).
Table 245 - Object Instances
Instance ID
Description
Address Switch Settings
0
Relay Module Class Instance
1
First Relay Expansion Module
SWI-SW2 as 0...1
2
Second Relay Expansion Module
SWI-SW2 as 1...0
3
Third Relay Expansion Module
SWI-SW2 as 1...1
Содержание 1444-AOFX00-04RB
Страница 10: ...10 Rockwell Automation Publication 1444 UM001D EN P June 2018 Table of Contents Notes...
Страница 12: ...12 Rockwell Automation Publication 1444 UM001D EN P June 2018 Preface Notes...
Страница 198: ...198 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 5 Configure the Tachometer Expansion Module Notes...
Страница 210: ...210 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 7 Configure Relays Notes...
Страница 230: ...230 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 8 Configure Alarms Notes...
Страница 240: ...240 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 9 Trend and Transient Capture Notes...
Страница 316: ...316 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 10 Operate the Module Notes...
Страница 549: ......