Rockwell Automation Publication 1444-UM001D-EN-P - June 2018
51
Install the Dynamix 1444 Series Monitoring System
Chapter 2
Upper Base Connector
Main Module Connectors
These connections provide duplicate terminals for twin, wide ranging DC
supplies (24V nominal).
You can use the duplicate terminals to daisy chain the power from one base to
the next (subject to an overall current limit and using a star connection to avoid
excessive voltage drop). There is internal diode protection against reverse
polarity and for the purposes of automatic supply selection when redundant
sources are connected to inputs 0 and 1. The supply side connections are
isolated from the remainder of the module circuitry.
Terminal
Name
Application
Description
49
RET_1
Module Power
Supply 1 Return
50
RET_1
51
+24V_1
Supply 1 +24V
52
+24V_1
53
RET_0
Supply 0 Return
54
RET_0
55
+24V_0
Supply 0 +24V
56
+24V_0
57
OVR
Buffered Outputs
Override High
58
OVR
Override Low
59
Shield
Shield
Cable shield connection points
60
Shield
61
Shield
62
Shield
63
Shield
64
Shield
56
55
54
53
52
51
50
49
+24V-0
+24V-0
RET_0
RET_0
+24V-1
+24V-1
RET_1
RET_1
Содержание 1444-AOFX00-04RB
Страница 10: ...10 Rockwell Automation Publication 1444 UM001D EN P June 2018 Table of Contents Notes...
Страница 12: ...12 Rockwell Automation Publication 1444 UM001D EN P June 2018 Preface Notes...
Страница 198: ...198 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 5 Configure the Tachometer Expansion Module Notes...
Страница 210: ...210 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 7 Configure Relays Notes...
Страница 230: ...230 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 8 Configure Alarms Notes...
Страница 240: ...240 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 9 Trend and Transient Capture Notes...
Страница 316: ...316 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 10 Operate the Module Notes...
Страница 549: ......