70
Rockwell Automation Publication 1444-UM001D-EN-P - June 2018
Chapter 2
Install the Dynamix 1444 Series Monitoring System
3-wire Acceleration Sensors or Other 3-wire Transducer Systems
Figure 29 - 3-wire Acceleration Sensor
Configure the channel for the appropriate polarity supply (+25V or -25 V). A
list of appropriate terminals for each channel follows. See
In general, most 3-wire transducer systems req25V or -25V at no more
than 25 mA can be accommodated by connecting like.
3-wire sensors are wired identically to eddy current probes (power polarity is
set in module configuration). See
…
for wiring illustrations.
2-wire Self-generating Velocity Sensors
If self-generating, no transducer power connection is required. A list of
appropriate terminals for each channel follows.
Also use this wiring solution for externally powered 2-wire sensors.
Typical Core Designation
Channel 0
Channel 1
Channel 2
Channel 3
Power Supply
1
5
9
13
SIG (+)
2 or 3
6 or 7
10 or 11
14 or 15
Return (-)
4
8
12
16
Typical Core Designation
Channel 0
Channel 1
Channel 2
Channel 3
SIG (+)
2 or 3
6 or 7
10 or 11
14 or 15
Return (-)
4
8
12
16
Содержание 1444-AOFX00-04RB
Страница 10: ...10 Rockwell Automation Publication 1444 UM001D EN P June 2018 Table of Contents Notes...
Страница 12: ...12 Rockwell Automation Publication 1444 UM001D EN P June 2018 Preface Notes...
Страница 198: ...198 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 5 Configure the Tachometer Expansion Module Notes...
Страница 210: ...210 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 7 Configure Relays Notes...
Страница 230: ...230 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 8 Configure Alarms Notes...
Страница 240: ...240 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 9 Trend and Transient Capture Notes...
Страница 316: ...316 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 10 Operate the Module Notes...
Страница 549: ......