Rockwell Automation Publication 1444-UM001D-EN-P - June 2018
273
Operate the Module
Chapter 10
Table 55 - Transducer Status
Table 56 - Speed Status
Tag
Description (if=1)
Ch0Enabled
Channel 0 Enabled
Channel is configured for dynamic or static measurements.
Ch1Enabled
Channel 1 Enabled
Channel is configured for dynamic or static measurements.
Ch2Enabled
Channel 2 Enabled
Channel is configured for dynamic or static measurements.
Ch3Enabled
Channel 3 Enabled
Channel is configured for dynamic or static measurements.
Transducer0Enabled
Transducer 0 Enabled
Set if Channel0Enabled is set, unless the sensor is self or externally powered, or is powered from
Channel 2 if a Dual Path personality is used.
Transducer1Enabled
Transducer 1 Enabled
Set if Channel1Enabled is set, unless the sensor is self or externally powered, or is powered from
Channel 3 if a Dual Path personality is used.
Transducer2Enabled
Transducer 2 Enabled
Set if Channel2Enabled is set, unless the sensor is self or externally powered, or is powered from
Channel 0 if a Dual Path personality is used.
Transducer3Enabled
Transducer 3 Enabled
Set if Channel3Enabled is set, unless the sensor is self or externally powered, or is powered from
Channel 1 if a Dual Path personality is used.
Transducer0Fault
Transducer 0 Fault
Transducer 0 fault. Indicates bias out of range and/or detected wire off condition.
Transducer1Fault
Transducer 1 Fault
Transducer 1 fault. Indicates bias out of range and/or detected wire off condition.
Transducer2Fault
Transducer 2 Fault
Transducer 2 fault. Indicates bias out of range and/or detected wire off condition.
Transducer3Fault
Transducer 3 Fault
Transducer 3 fault. Indicates bias out of range and/or detected wire off condition.
Transducer0WireOffDetected
Transducer 0 Wire Off Detected
Transducer 0 wire off condition detected.
Transducer1WireOffDetected
Transducer 1 Wire Off Detected
Transducer 1 wire off condition detected.
Transducer2WireOffDetected
Transducer 2 Wire Off Detected
Transducer 2 wire off condition detected.
Transducer3WireOffDetected
Transducer 3 Wire Off Detected
Transducer 3 wire off condition detected.
Tag Description
(if=1)
Speed0Enabled
Speed 0 Enabled
Speed 0/1 is enabled. Since the AOP does not provide an "OFF" selection, these must always be set.
Speed1Enabled
Speed 1 Enabled
Tach0Fault
Tach (Speed) 0 Fault
Speed 0/1 is in fault. Fault detection / indication depends on the speed Source selection.
The fault indication is associated with any type of speed input.
Tach1Fault
Tach (Speed) 1 Fault
Содержание 1444-AOFX00-04RB
Страница 10: ...10 Rockwell Automation Publication 1444 UM001D EN P June 2018 Table of Contents Notes...
Страница 12: ...12 Rockwell Automation Publication 1444 UM001D EN P June 2018 Preface Notes...
Страница 198: ...198 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 5 Configure the Tachometer Expansion Module Notes...
Страница 210: ...210 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 7 Configure Relays Notes...
Страница 230: ...230 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 8 Configure Alarms Notes...
Страница 240: ...240 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 9 Trend and Transient Capture Notes...
Страница 316: ...316 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 10 Operate the Module Notes...
Страница 549: ......