7
–
*71
PAGER PHONE # FOR OPENS/CLOSES
Enter 0-9 for each digit. Enter #11 for *, #12 for #,
#13 for 2 second pause
*72
PAGER ID # FOR OPENS/CLOSES
Enter up to 10 digits for the pager id #
*73
PAGER PHONE # FOR SYSTEM
Enter 0-9 for each digit. Enter #11 for *, #12 for #,
#13 for 2 second pause
*74
PAGER ID # FOR SYSTEM
Enter up to 10 digits for the pager id #
*75
PAGER PHONE # FOR TEST
Enter 0-9 for each digit. Enter #11 for *, #12 for #,
#13 for 2 second pause
*76
PAGER ID # FOR TEST
Enter up to 10 digits for the pager id #
ZONE TYPE RESTORE ENABLES
*
79
FOR ZONE TYPES 1-8
*80
FOR TYPES 9/10
1
2
3
4
5
6
7
8
9
10
1=enable; [0=disable]
*83
FIRST TEST REPORT TIME
| | |
[Day 00; hour 12; min 00] Days 01-07 Hours 00-23 Min 00-
59; 00 in all boxes=instant (Day 01= Monday)
*84
SWINGER SUPPRESSION
[03]
|
01-15 alarms; Must be "00" (disabled) for UL
.
*85
ENABLE DIALER REPORTS [0]
FOR PANICS & DURESS
995 996 999 Duress
1=enable; 0=disable
*87
ENTRY WARNING
[1]
1=continuous; 0=3 beeps
*88
BURG. ALARM COMM. DELAY
[0]
1=16 seconds; 0=no delay. Must be "0" for UL Commercial
Burg. installations.
*89
RESTORE REPORT TIMING
[0]
0=Instant; 1=After bell timeout if zone is restored; 2=when
system is disarmed. Must be "0" for fire or UL Commercial
Burg. installations.
*90
SEC. SUBS. ACCT #
| | | |
Enter 00-09; B-F (11-15) [15 15 15 15]
1*17
LOBBY PARTITION
[0]
Enter the "common lobby" partition (1-2)
1*18
AFFECTS LOBBY
[0]
Enter 1 if this partition affects the common lobby; enter 0 if it
does not. Must be "0" for Commercial Fire & UL installations.
1*19
ARMS LOBBY
[0]
Enter 1 if arming this partition attempts to arm lobby; enter 0
if it does not. Must be "0" for Commercial Fire & UL
installations.
1*20
EXIT ERROR LOGIC
[0]
0=No, 1=Bypass E/E and Interior zones faulted after exit
delay. Must be "0" for Commercial Fire & UL installations.
1*21
EXIT DELAY RESET
[0]
0=No; 1=Resets Exit Delay to 60 seconds after zone is
closed. Must be "0" for Commercial Fire & UL installations.
FIELDS 1*22-1*25: Allow four sets of two zones each to be
linked so that both must fault within a five minute period to
cause an alarm.
1*22
CROSS-ZONING PAIR ONE
| | | |
1*23
CROSS-ZONING PAIR TWO
| | | |
1*24
CROSS-ZONING PAIR THREE
| | | |
1*25
CROSS-ZONING PAIR FOUR
| | | |
1*26
PANIC BUTTON OR SPEEDKEY
[00, 00, 00, 00]
|
|
|
|
A B C
D
Enter speedkey macro # (01-35) to use keys A-C for macro.
Otherwise enter 00 to use as panic. For D key, enter macro
# or 00 to select macro when key is pressed.
MISCELLANEOUS WIRELESS OPTIONS
Fields 1*28 - 1*31 are not applicable to Commercial
Fire or UL installations.
1*28
RF TX LOW BATTERY SOUND
[0]
1=immediate; 0=when disarmed
1*29
RF TX LOW BATTERY REPORT ENABLE [0]
1=enable; 0=disable
1*30
RF RCVR CHECK-IN INTERVAL
[06]
|
02-15 times 2 hours; 00 disables supervision
1*31
RF TRANSMITTER CHECK-IN INTERVAL[12]
|
02-15 times 2 hours; 00 disables transmitter supervision
1*33
TOUCH-TONE W/ROTARY BACKUP
[0]
1=enable; 0=disable
1*34
COMM. SPLIT REPORT SELECTION
[0]
0=no; 1=alarms and alarm restores primary, others secondary;
2=open/close, test secondary, others primary; 3 = fire alarms
& troubles primary, all secondary. See
✴
51 for comments if
using with dual reporting.