– 33 –
If using options 56 or 57 (usually as the STOP Zone Type), data fields 1
✱
74 and 1
✱
75 for the respective
relay timeouts for minutes and seconds must be programmed.
02 START: ACS PT
(00-31) 00
If the start zone type selected was 27 (access point), this prompt will be displayed. Enter the
access point (00-31) which will start the Output action.
Press [
✱
] to continue.
02 START: PARTN
ANY PARTITION
0
If the starting event will be limited to occurring on a specific partition, enter the partition number
(1-2) in which the start event will occur. Enter 0 for any partition.
Press [
✱
] to continue.
02 STOP: ZN LIST
00
If a zone list is being used to stop this Output action, enter the zone list number 1-15. The
restore of a zone on the Zone List will stop the Output. If a zone list is not being used, enter 0.
Press [
✱
] to continue.
02 STOP: ZN TYPE
NO RESPONSE
00
If a Zone Type/System Operation is being used to stop the Output action, enter the 2-digit
code as listed in the Choices for Start/Stop System Operation chart.
Press [
✱
] to continue.
02 STOP: ACS PT
(00-31) 00
If the stop zone type selected was 27 (access point), this prompt will be displayed. Enter the
access point (00-31) which will stop the Output action.
Press [
✱
] to continue.
02 STOP: PARTN
ANY PARTITION
0
This is the partition to which the stop condition will be limited. Enter 0 for any partition. Enter
1-2 for specific partition number.
Press [
✱
] to continue.
02 OUTPUT GROUP
00
Outputs may be grouped for common activation by time-driven events (commands 06-10).
Enter 00 (no group) or 01-15 for a specific group number.
Press [
✱
] to continue.
02 RESTRICTION
1=YES 0=NO
0
The system may have some devices, which are not intended to be under end user control,
such as Outputs activating fire doors or machinery. Enter 1 if the end user will be restricted
from accessing this Output group.
Press [
✱
] to continue.
02 OUTPUT TYPE
V-PLEX
0
Enter 0 for V-Plex (polling loop) devices. Enter 1 for (ECP) relay modules (4204/4204CF).
Enter 3 for (FSA) Fire System Annunciator.
Press [
✱
] to continue.
02 V-PLEX ZONE #
000
For polling loop trigger outputs (4101SN), enter the protection zone number (001-032) linked to
each output, if used. Be sure to enroll the module’s serial number (see Zone Programming
prompt earlier in this section).
Press [
✱
] to continue.
02 ECP ADDRESS
00
If 1 was selected for relay modules (4204/4204CF), enter the actual relay module's address
(01-15) as set by its DIP switches. Up to 8 modules can be installed in a system.
Press [
✱
] to continue.
02 MODULE RELAY#
0
For 4204 Relay Outputs, enter the specific relay number on that module (1-4). For 4204CF
outputs,
enter only module relay number 1 (Output A) or relay number 3 (Output B).
These are the only two programmable relays on the 4204CF Module.
Press [
✱
] to continue.
The keypad will display the Start and Stop summary screens again.
Press [
✱
] to continue.
02 ECP ADDRESS
00
If 3 was selected for FSA, enter the actual FSA's address (08-23) as set by its DIP switches.
Up to 4 modules can be installed in a system.
Press [
✱
] to continue.