Output Devices Programming
From Data Field Programming Mode, press #93 to display the "ZONE PROG?" prompt. Press 0 (NO) to each menu option
until the "OUTPUT PGM?" prompt appears. Press 1 (YES).
While in this mode, press [
✱
] to advance to next screen. Press [#] to backup to the previous screen.
ENTER OUTPUT #
(00=QUIT) 01
Enter the Output identification number 01-96. This is a reference number only, used for
identification purposes. The actual module address and relay number on the module are
programmed in the last two prompts.
Press [
✱
] to continue.
02 A EV ZL ZT P
STT 0 0 00 00 0
Press [
✱
] to continue.
02 A ZL ZT P
STOP 0 00 00 0
The keypad will display a summary STOP screen.
Press [
✱
] to continue.
02 OUTPUT ACTION
NO RESPONSE
0
The Output Action is the way in which the Output will respond when activated by the "start"
event. Enter the desired action for this Output as follows:
0=not used; 1=close for 2 secs.; 2=stay closed; 3=pulse on/off; 4= toggle on/off alternately
02 START EVENT
NOT USED
0
A Output may be activated either by an Event used in conjunction with a Zone List, and/or by
a Zone Type/System Operation. If using an Event/Zone List combination, enter the event code
as follows:
0=not used; 1=alarm; 2=fault; 3=trouble; 4=restore
If not using a Zone List to activate the Output, enter 0.
Press [
✱
] to continue.
02 START: ZN LIST
00
A Zone List is a set of zones that can be used to initiate the start or stop Output action. If a
zone list is being used to start this Output action, enter the Zone List number 1-15. If a zone list
is not being used, enter 0.
Press [
✱
] to continue.
02 START: ZONE #
000
A specific zone can be used instead of or in addition to an Event/Zone List or Zone
Type/System Operation combination to start the Output action. Enter the 3-digit zone number.
Press [
✱
] to continue.
02 START: ZN TYPE
NO RESPONSE
00
A Zone Type/System Operation can be used instead of or in addition to an Event/Zone List
combination or a specific zone to start the Output action. If a Zone Type/System Operation is
being used, enter the 2-digit code as listed below.
Press [
✱
] to continue.
Choices for Start/Stop Zone Types and System Operation:
00 = No Response (Not Used)
44 = RF Low Battery
01 = Entry/Exit #1
27 = Access Point (allows more than
one relay to be controlled by
activation if access point request)
45 = Polling Loop Failure
02 = Entry/exit #2
28 = MLB Supervision
47 = Console Failure
03 = Perimeter
29 = Momentary on Exit ***
51 = RF Receiver Failure
04 = Interior Follower
30 = On Second Code + Off
52 = Kissoff
05 = Trouble Day/Alarm Night
31 = End of Exit Time
54 = Fire Zone Reset
06 = 24-Hr. Silent
32 = Start of Entry Time
55 = 1 Minute
07 = 24-Hr. Audible
33 = Any Burglary Alarm
08 = 24-Hr. Auxiliary
34 = Code + [#] + 71 Key Entry
56 = XX Minutes (enter XX in field 1*74) *
09 = Fire Alarm or Trouble
35 = Code + [#] + 72 Key Entry
10 = Interior W/Delay
36 = At Bell Timeout **
57 = YY Seconds (enter YY in field 1*75)*
16 = Fire With Verification
37 = 2 Times Bell Timeout **
58 = Duress
17 = Fire Waterflow ****
38 = Chime
18 = Fire Supervisory
39 = Fire Alarm
19 = 24-Hr. Trouble
40 = Bypassing
60 = Audio Alarm Verification (must be
selected for both START and STOP
operation)
20 = Arming-STAY
41 = AC Power Fail
61 = Code + [#] + 67 Key Entry
21 = Arming-AWAY
42 = System Battery Low
62 = Bell 2 Timeout
22 = Disarming ([Code] + Off)
43 = Communication failure
63 = Aux. Relay Timeout
23 = No Alarm Response
*Stop condition only, **Or at Disarming, whichever occurs earlier, ***Used with VistaKey door access modules,
**** If zone type 17 (waterflow) is selected, an event of fault or alarm should be used as the output start option.