14
–
↓
Zone Number
010 ZONE TYPE
PERIMETER
03
Zone Type 03 entry
shown
† These are special
zone types used with
5800 Series Wireless
Pushbutton Units which
will result in arming the
system in the STAY or
AWAY mode, or
disarming of the system,
depending on the
selection made.
Each zone must be assigned a zone type, which defines the way in which the system responds
to faults in that zone. Refer to the
Zone Type Definitions section in the VISTA-32FB
Installation and Setup Guide for detailed definitions of each zone type. Enter the zone type
desired (or change it, if necessary). Available zone types are listed below.
00 = Assign for Unused Zones
17 = Fire Waterflow
01 = Entry/Exit #1, Burglary
18 = Fire Supervisory
02 = Entry/Exit #2, Burglary
19 = 24-Hour Trouble
03 = Perimeter, Burglary
20 = Arm–STAY†
04 = Interior Follower, Burglary
21 = Arm AWAY†
05 = Trouble Day/Alarm Night
22 = Disarm†
06 = 24 Hr. Silent Alarm
23 = No Alarm Response
07 = 24 Hr. Audible Alarm
(e.g., Relay activation)
08 = 24 Hr. Auxiliary
27 = Access Point
09 = Fire Without Verification
28 = MLB Supervision
10 = Interior Delay, Burglary
(if VGM installed)
16 = Fire With Verification
29 = Momentary on Exit*
* Used with VistaKey door access modules.
Press [
✱
] to continue.
010 PARTITION
1
Enter the partition number (1–2) you are assigning this zone to.
Press [
✱
] to continue.
010 REPORT CODE
1st 03 2nd 12
3C
Enter the report code. The report code consists of 2 hexadecimal digits, each in turn consisting
of 2 numerical digits. For example, for a report code of "3C", enter 03 for "3" and 12 for "C."
(Refer to
System Communication section for more information about report codes and report
code formats.)
Press [
✱
] to continue.
010 INPUT TYPE
RF Xmitter
3
Note that input types 4 &
5 are valid for certain
5800 Series transmitters
only (e.g., 5801, 5802,
5802CP & 5803).
Input type 10 is
applicable only if
PassPoint ACS is
installed with the Vista
Gateway Module.
If response type 28 was
selected, the input type
MUST be 00.
Enter the input device type as follows:
00 = not used
01 = hardwired
03 = supervised RF transmitter (RF type)
04 = unsupervised RF transmitter (UR type)
05 = RF button-type transmitter (BR type)
06 = serial number polling loop device (SL type)
07 = DIP switch-type polling loop device
08 = right loop of DIP switch type device.
09 = keypad input (code + #73)
10 = PassPoint ACS input
11 = VistaKey Door Status Monitor (DM)*
12 = VistaKey Request to Exit (RE)*
13 = VistaKey General Purpose (GP*)
Right loops refer to the use of the right loop on a 4190WH Zone Expander Module and/or 4278
PIR, which allow hardwired devices to be monitored by the polling loop.
If programming hardwired, or DIP switch polling loop devices, the summary display appears
after completing this entry.
* Only used with VistaKey door access modules.
Press [
✱
] to continue.
010 ACCESS POINT
(00-31)
01
If response type 27, 29 or input types 11 – 13 was selected, this prompt will be displayed.
Enter the access point to be controlled by the input type (00-31 for type 27; 01-15 for type 29;
01-15 for types 11 - 13).
Note: This prompt also appears when the input type selected is 06. For standard SL, the
selected address must be 00.
Note: If you are using the VistaKey module, the access point must match the address that was
set in the module.