–
3
–
Recommended Programming Procedure
The following is a step-by-step procedure recommended for programming your VISTA-32FB system.
1.
Set the keypads (and other peripheral devices) to the appropriate addresses.
2.
Set factory defaults by pressing
✱
97.
This will automatically enable keypad addresses 00-01, so be sure at least one keypad is set to one of these
addresses
3.
Program system-wide (global) data fields.
Using the programming form as a guide, enter program mode and program all system wide programming
fields. These options affect the entire system, regardless of partitions. They include control options,
downloader and dialer options, RF options, event logging options, etc. Refer to the COMPLETE LIST OF
PROGRAMMING FIELDS for a listing of the program fields arranged by function.
Note that field 2
✱
00 (number of partitions) must be programmed before continuing.
4.
Program partition-specific fields.
After the system-wide fields have been programmed, program all partition-specific programming fields by first
pressing
✱
91 to select a partition (while still in data field program mode). Then enter the first partition-specific
field number
✱
09. The next partition-specific field will automatically be displayed when you are finished
entering the value for field
✱
09. Partition-specific fields can have different values for each partition. To
program the fields for the next partition, press
✱
91, enter the desired partition number, then enter field
✱
09.
Refer to the
MECHANICS OF PROGRAMMING
section in the
VISTA-32FB Installation and Setup Guide
for
detailed instructions.
5.
Use #93 Menu Mode for device programming.
Refer to the
Device Programming
in this guide to assign keypad ID numbers and default partitions for each
keypad, and to selectively suppress certain keypad sounding options. Also use this mode to assign RF
receivers, relay modules, the VIP module, the ECP Long Range Radio, and the Vista Gateway Module.
6. Use #93 Menu Mode for zone programming.
Refer to the
Zone Programming
in this guide to program zone response types, assign right loop zones and
wireless zones, assign zones to partitions, and to program alarm report codes.
7. Use #93 Menu Mode for programming outputs.
Refer to the
Output Programming
in this guide to program desired output operation.
8. Program Communication options.
Refer to
System Communication
section in the
VISTA-32FB Installation and Setup Guide
for detailed
instructions, then use #93 menu mode to program report codes.
9. Use #93 Menu Mode for programming alpha descriptors.
Refer to the
Alpha Programming
in this guide to enter zone and partition descriptors and a custom installer's
message.
10. Use #93 Menu Mode for relay voice descriptors and custom word substitutes.
Refer to the
Relay Voice Descriptors
in this guide for further instructions for programming relay descriptors to
be annunciated by the VIP module, as well as the
Custom Index
section for custom word substitutes.
11. Use #80 Mode for programming schedules.
Refer to the
Scheduling Menu Prompts
in the guide to program open/close schedules, temporary and holiday
schedules, limitation of access schedules, and time driven events.
12. Define user access codes.
Refer to
User Access Codes
section in the
VISTA-32FB Installation and Setup Guide
to program authority
level, O/C reporting option, partition assignments, and wireless key assignments for each user.
13. Exit Programming Mode.
Exit programming mode by pressing either
✱
98 or
✱
99. Additional entries of
✱
99 is required if the exit is being
done from fields 1
✱
00 and above.
To prevent re-access to programming mode using the Installer's code, use
✱
98. The only way to re-access
programming mode is by depressing both the [
✱
] and [#] keys at the same time within 30 seconds of power
up.
Exiting by using
✱
99 always allows reentry into programming mode using the Installer's code. Either way of
exiting will allow access via downloading. Note that if local programming lockout is set via downloading,
programming mode cannot be entered at the keypad.
www.PDF-Zoo.com