10
–
SUMMARY OF PROGRAMMING COMMANDS
•
To enter program mode, enter installer code + [8] + [0] + [0]
•
To set standard defaults, press *97
•
To change to next page of program fields, press *94
•
To return to previous set of fields, press *99
•
To erase account & phone number field entries, press [*] + field [*]
•
To assign zone descriptors, press #93 + follow menu prompts
•
To add custom words, press #93 + follow menu prompts
•
To enter Installer's Message, press #93 + follow menu prompts
•
To exit program mode, press *99 OR *98: *99 allows re-access to programming mode
by installer code. *98 prevents re-access to programming mode by installer code.
Partition-Specific Fields
(Duplicate this page for each partition in the installation.)
To program these fields,
1. Press *91 to select a partition.
2. Enter a partition-specific field number (ex. *09).
3. Make the required entry.
4. Repeat steps 1-3 for each partition in the system.
PARTITION #____ PROGRAM FIELDS
1st Page Fields
*09
ENTRY DELAY #1
[02]
|
00-15 times 15 seconds. Maximum 03 for UL Listed
installations.
*10
EXIT DELAY #1
[03]
|
00-15 times 15 seconds. Maximum 04 for UL Listed
installations.
*11
ENTRY DELAY #2
[06]
|
00-15 times 15 seconds. Maximum 03 for UL Commercial
Burglary installations.
*12
EXIT DELAY #2
[08]
|
00-15 times 15 seconds. Maximum 04 for UL Commercial
Burglary installations.
*13
BELL 1 TIMEOUT
[04]
|
01-15 times 2 minutes. Minimum 16 minutes for UL.
Commercial Burglary and 6 minutes for Commercial Fire
installations.
*16
CONFIRMATION OF ARMING DING
[0]
1=enable; 0=disable. Must be "1" for UL Commercial
Burglary installations.
*22
KEYPAD PANIC ENABLES
[001]
1=enable; 0=disable
995 996 999
*23
MULTIPLE ALARMS
[1]
1=yes; 0=no. Enter 1 for Commercial Fire & UL Commercial
Burglary installations.
*29
QUICK ARM
[1]
1=yes; 0=no
*32
PRIM. SUBS. ACCT #
| | | |
Enter 00-09; B-F (11-15) [15 15 15 15]
*38
PREVENT ZONE XXX BYPASS
[000]
| |
001-032; 000 if all zones can be bypassed
*39
ENABLE OPEN/CLOSE REPORT
[1]
FOR INSTALLER CODE
1=enable; 0=disable
*84
SWINGER SUPPRESSION
[03]
|
01-15 alarms; Must be "00" (disabled) for Commercial Fire &
UL installations..
*85
ENABLE DIALER REPORTS[0]
FOR PANICS & DURESS
995 996 999
Duress
1=enable; 0=disable
*87
ENTRY WARNING
[0]
1=continuous; 0=3 beeps
*88
BURG. ALARM COMM. DELAY
[0]
1=16 seconds; 0=no delay. Must be "0" for UL Commercial
Burglary installations.
*90
SEC. SUBS. ACCT #
| | | |
Enter 00-09; B-F (11-15) [15 15 15 15]
1*18
AFFECTS LOBBY
[0]
Enter 1 if this partition affects the common lobby; enter 0 if it
does not.
1*19
ARMS LOBBY
[0]
Enter 1 if arming this partition attempts to arm lobby; enter 0
if it does not