background image

 21 

 –

Report Code Programming

All report codes are entered using 

# 93 Menu Mode Programming, either through Report Code Programming or through the

Zone Programming while entering other zone information.  In the VISTA-32FB, reports are divided into six categories.  These
categories represent the main menu options found in 

Report Code Programming.  Reports and the categories in which they

are found are as follows:

ALARM CODES

RESTR, SUPV. CODES
(for groups of 16 zones)

SYSTEM GROUP #1

Zone Alarm Reports

Alarm Restore
Trouble
Trouble Restore
Bypass
Bypass Restore

Closing (Arm Away)
Opening (Disarm)
System Low Battery
Low Battery Restore
AC Loss
AC Restore
Periodic Test
Power
Cancel
Program Tamper

SYSTEM GROUP #2

SYSTEM GROUP #3

SYSTEM GROUP #4

Arm STAY
Time Set, Log Reset
Log 50%, 90% Full
Event Log Overflow
Exit Error by Zone
Exit Error by User
Recent Close

Early Open
Early Close
Late Open
Late Close
Failed to Open
Failed to Close
Auto-Arm Failed
Schedule Change

Fire Walk-Test Start
Fire Walk-Test End
Off-Normal

The programming sequence that follows assumes that all reports for the system will be entered at one time.  In actuality, it is
possible to skip from one main menu option to another by pressing 0 (NO) at each main menu option.  Main menu options are
highlighted in bold text.  To enter report codes, do the following:

Enter Program Mode [Installer Code] + [8 0 0].  Then press #93.  Enter 0 (NO) at each main menu option until the REPORT
CODE PROG

 prompt is displayed.

REPORT CODE PROG

1 = YES    0 = NO      0

Press 1 (YES) to enter 

Report Code Programming.

Zone Alarm Reports

ALARM, ID DIGIT?

1 = YES    0 = NO      0

Press 1 (YES) to enter Alarm Report Codes for zones.  Press 0 (NO) to skip to the next main
menu option.

ENTER ZONE NO.

000 = QUIT            001

Enter the zone number for which you are entering the report code.
Press [

to continue.

001  REPORT CODE

1st  00  2nd  00       000

Enter the first digit of the Alarm report code (double-digit entry) and press [

].  Enter the second

digit of the Alarm Report Code.
Press [

] to continue.

ENTER ZONE NO.

000 = QUIT            001

Enter the zone number for which the Report Code is being entered.  When all zone Alarm Codes
have been programmed, enter 000 to Quit.
Press [

to continue.

QUIT REPORT MENU

1 = YES   0 = NO      0

If you have completely finished entering report codes, press 1 (YES) to quit 

Report Code

Programming.  If you wish to enter other system report codes, enter 0 (NO).
Press [

] to continue.

www.PDF-Zoo.com

Содержание VISTA-32FB

Страница 1: ...K3840V1 9 00 9 9 6 67 7 RPPHUFLDO LUH DQG XUJODU 3DUWLWLRQHG 6HFXULW 6 VWHP ZLWK 6FKHGXOLQJ 3URJUDPPLQJ XLGH FIRE FIRE PULL www PDF Zoo com...

Страница 2: ...ne alpha keypad is connected to the control and is set to device address 00 Single Partition System The system default is for a single partition system Use the VISTA 32FB SINGLE PARTITION PROGRAMMING...

Страница 3: ...eway Module 6 Use 93 Menu Mode for zone programming Refer to the Zone Programming in this guide to program zone response types assign right loop zones and wireless zones assign zones to partitions and...

Страница 4: ...Communications 90 Partition Specific 1 01 93 Menu Mode 1 02 93 Menu Mode 1 03 93 Menu Mode 1 04 93 Menu Mode 1 05 93 Menu Mode 1 06 93 Menu Mode 1 07 93 Menu Mode 1 08 93 Menu Mode 1 09 93 Menu Mode 1...

Страница 5: ...hrs 0 normal report about 2 min after AC loss Must be 2 for Central and Remote Station Fire alarm systems 20 VIP MODULE PHONE CODE Enter 01 09 for the first digit enter 00 11 11 for or 12 for for the...

Страница 6: ...go to secondary only If used with Split Reporting 2 option alarms and alarm restores go to both open close and test messages go to secondary only while all other reports go to primary If used with Spl...

Страница 7: ...ial Fire UL installations 1 19 ARMS LOBBY 0 Enter 1 if arming this partition attempts to arm lobby enter 0 if it does not Must be 0 for Commercial Fire UL installations 1 20 EXIT ERROR LOGIC 0 0 No 1...

Страница 8: ...es of 2 minutes desired for 80 Menu Mode time driven event relay command numbers 04 09 and 93 Menu Mode Output Programming command 56 1 75 RELAY TIMEOUT YY SECONDS 000 Enter the relay timeout 0 127 se...

Страница 9: ...waterflow restores 3 15 ALARM BELL SOUND 1 0 0 pulsed 1 steady Bell 1Bell 2 3 16 DELAY for ZONE TYPES 17 18 00 Waterflow FIre Supv Enter 00 15 times 2 seconds 3 17 ALTERNATE FUNCTION TAMPER 0 FOR ZONE...

Страница 10: ...r UL Commercial Burglary installations 12 EXIT DELAY 2 08 00 15 times 15 seconds Maximum 04 for UL Commercial Burglary installations 13 BELL 1 TIMEOUT 04 01 15 times 2 minutes Minimum 16 minutes for U...

Страница 11: ...enings and closings occurring outside the scheduled opening closing windows will trigger dialer reports Opening reports will also be suppressed during the closing window in order to prevent false repo...

Страница 12: ...lows ZONE PROG 1 YES 0 NO For programming the following Zone Number Zone Response Type Partition Number for Zone Dialer report code for zone Bell aux relay assignment for zone Input Device Type for zo...

Страница 13: ...screen Press to display a previous screen SET TO CONFIRM 0 NO 1 YES 0 This prompt will appear once upon entering Zone Programming If Yes Confirmation prompts will be displayed after the device s Seri...

Страница 14: ...nd 12 for C Refer to System Communication section for more information about report codes and report code formats Press to continue 010 INPUT TYPE RF Xmitter 3 Note that input types 4 5 are valid for...

Страница 15: ...ess and release the button a second time OR b Manually enter the 7 digit serial number printed on a label on the transmitter using the Alpha keypad Then press the key the cursor will move to the L pos...

Страница 16: ...HOUSE CODE YOU MUST ENROLL THIS BUTTON LOOP 1 5809 ENROLL AS RF 5801 ENROLL AS UR OR RF LOOP 3 LOOP 1 LOOP 2 LOOP 4 YOU MUST ENROLL THIS BUTTON Note For information on any transmitter not shown above...

Страница 17: ...est each using the system s Test Mode Do not use the Transmitter ID Sniffer Mode for this The system will check only for transmission of one zone on a particular transmitter NOT the zones assigned to...

Страница 18: ...reen Use the A key to move to the right Use the B key to move to left and to back up to B field Press to accept existing information 010 INPUT S N L A XXX XXXX If you entered RF BR UR or SL for the In...

Страница 19: ...e type etc relevant to that device Entering Wireless Keys If the D key was previously pressed to enter defaults for 5804 and or 5804BD wireless keys the following screens will appear FROM TEMPLATE 1 6...

Страница 20: ...Zone No prompt and will show the lowest numbered zone of the next available 4 zone group consecutive zones that is available for programming When all zones have been programmed enter 000 to quit Afte...

Страница 21: ...tem will be entered at one time In actuality it is possible to skip from one main menu option to another by pressing 0 NO at each main menu option Main menu options are highlighted in bold text To ent...

Страница 22: ...016 00 Enter the first digit of the Bypass Restore Report Code double digit entry and press The second digit for two digit reporting formats is automatically the ID second digit of the Alarm Report Co...

Страница 23: ...number is desired as the second digit enter 01 not necessary for Contact ID or High Speed formats Press to continue Enter the rest of the codes in the same manner Other codes in System Group 3 are Ear...

Страница 24: ...ck to 93 Menu Mode 4 Refer to the sections that follow for procedures for adding alpha descriptors Zone Descriptors 1 Select ZONE DESCRIPTOR mode The keypad keys perform the following functions 3 Scro...

Страница 25: ...hat there are only 16 character spaces on each of the two lines To create a custom display message proceed as follows 1 Select Default Screen Mode The keypad will ask for the partition number for this...

Страница 26: ...s 3 to advance through the list of symbols numbers and letters Press 1 to move back through the list When the desired character has been reached press 6 to select it The cursor will then move to the r...

Страница 27: ...MEDICAL 135 MEDICINE 136 MICROWAVE 137 MONEY 138 MONITOR 139 MOTHERS 140 MOTION 141 MOTOR 142 MUD 143 NORTH 144 NURSERY 145 OFFICE 146 OIL 147 OPEN 148 OPENING 149 OUTSIDE 150 OVERFLOW 151 OVERHEAD 15...

Страница 28: ...er 01 to maximum number of partitions programmed for system in field 2 00 This is the primary partition for which the device is intended to be used Enter 9 to make this keypad a master keypad for the...

Страница 29: ...Key Normal Key Function SHIFT Key Function BS ESC BS Press to delete entry ESC Press to quit Program Mode Also can reset EEPROM defaults Scroll down programming Scroll up programming N Y N Press for N...

Страница 30: ...F will not be displayed for private system users BAT PRESENT Y N N Enter Y if optional battery will be used Must be Y for UL installations a battery must be installed USE RADIO Y N N If Y is selected...

Страница 31: ...ere are no other zones of this type which are not to activate this device then ZONE TYPE may be used instead of using a ZONE LIST and EVENT to activate the device If a System Operation such as DISARMI...

Страница 32: ...List or Zone Type System Operation combination to start the Output action Enter the 3 digit zone number Press to continue 02 START ZN TYPE NO RESPONSE 00 A Zone Type System Operation can be used inst...

Страница 33: ...OUTPUT GROUP 00 Outputs may be grouped for common activation by time driven events commands 06 10 Enter 00 no group or 01 15 for a specific group number Press to continue 02 RESTRICTION 1 YES 0 NO 0 T...

Страница 34: ...more zones in that zone list Enter 0 if no changes are necessary If 1 is entered the following screen will appear otherwise the Enter Zone LIST prompt will reappear 01 Zn to DELETE 000 QUIT 000 Enter...

Страница 35: ...r 116 Alarm 255 And 067 Apartment 117 Appliances 161 Area 118 Attic 119 Baby 120 Back 121 Bar 122 Basement 021 Bathroom 051 Battery 053 Bed 092 Bedroom 015 Blower 123 Boiler 124 Bright 162 Building 12...

Страница 36: ...ress to accept entry The CUSTOM WORD NO prompt will be displayed Enter the next custom word number to be substituted or enter 00 to quit System Layout Worksheets As with any security system you should...

Страница 37: ...ion During Entry Console Annunciation During Exit Confirmation of Arming Ding for Bell 1 Confirmation of Arming Ding for Bell 2 Aux Rly Chime on Bell 1 Chime on Bell 2 Aux Relay Access Control Relay f...

Страница 38: ...d Entry Exit Beeps 02 Suppress Chime Mode Beeps Only 03 Suppress Arm Disarm Entry Exit and Chime Mode Beeps Defaults Addresses 00 01 Alpha Keypad No Suppression ACCESS CODES USER DEFINITIONS FOR PARTI...

Страница 39: ...Parti tion 1 2 Input Type 1 13 Serial Device Loop Bell Relay Activation Report Code Zone Information part numbers Alpha Descriptor 3 words max 01 02 03 04 05 06 07 08 09 010 011 012 013 014 015 016 01...

Страница 40: ...31 032 ZONE DEFINITIONS FOR KEYPAD PANIC ZONES 995 996 999 Enter yes no for each partition field 22 Zone No Zone Type 1 2 Bell Rel Act Report Code Zone Information part numbers Alpha Descriptor 3 word...

Страница 41: ...9 602 610 603 611 604 612 605 613 606 614 607 615 608 616 ZONE DEFINITIONS FOR SUPERVISORY OF ECP DEVICE ZONES 800 831 Zone No Zone Type Report Code Zone Information part numbers Alpha Descriptor 3 wo...

Страница 42: ...ght burglary 29 Momentary on exit Input Types 00 not used 08 right loop dip switch polling loop 01 hardwired 09 keypad input 03 supervised RF transmitter 10 PassPoint ACS input 04 unsupervised RF tran...

Страница 43: ...ation instructions as you enter the data during the displays and prompts that appear in sequence Notes For 4204 4204CF and FSA the Device Programming section must be programmed for the device address...

Страница 44: ...S T O P OUTPUT DEV A EV ZL Zone ZT P ZL ZT P Output Group Restrict 0 V Plex 1 4204 3 FSA V Plex Zone or Dev Add 4204 or FSA Relay for 4204 or LED for FSA 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35...

Страница 45: ...S T O P OUTPUT DEV A EV ZL Zone ZT P ZL ZT P Output Group Restrict 0 V Plex 1 4204 3 FSA V Plex Zone or Dev Add 4204 or FSA Relay for 4204 or LED for FSA 46 47 48 49 50 51 52 53 54 55 56 57 58 59 61...

Страница 46: ...S T O P OUTPUT DEV A EV ZL Zone ZT P ZL ZT P Output Group Restrict 0 V Plex 1 4204 3 FSA V Plex Zone or Dev Add 4204 or FSA Relay for 4204 or LED for FSA 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86...

Страница 47: ...ght 29 Momentary on Exit 54 Fire Zone Reset 06 24 Hr Silent 30 On Second Code Off 55 Disarm 1 Minute 07 24 Hr Audible 31 End of Exit Time 08 24 Hr Auxiliary 32 Start of Entry Time 56 XX Minutes enter...

Страница 48: ...Zone List 1 Started or stopped by zone numbers enter 000 to end entries Zone List 2 Started or stopped by zone numbers enter 000 to end entries Zone List 3 Started or stopped by zone numbers enter 00...

Страница 49: ...r 000 to end entries Zone List 12 Started or stopped by zone numbers enter 000 to end entries Zone List 13 Started or stopped by zone numbers enter 000 to end entries Zone List 14 Started or stopped b...

Страница 50: ...window for each day of the week and holidays Holidays 1 Yes 0 No 0 For defining up to 16 holidays for which partitions they apply Timed Events 1 Yes 0 No 0 For defining up to 20 time driven events wi...

Страница 51: ...17 18 19 20 Keep this worksheet handy as you will be asked for a given time window number later in this section Since the time windows are shared among all partitions it is important to make sure that...

Страница 52: ...r in sequence HOL Partition Month Day 1 2 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Time Driven Event Worksheet The system provides up to 20 time driven events that can be programmed for the system Fill...

Страница 53: ...lose Windows Action Specifier for commands 40 41 is Partition s for 42 is Access Group and for 50 no specifier is programmed Activation time 3 During is the only valid choice for these commands 40 Ena...

Страница 54: ...4 5 6 7 8 Temporary Schedule 81 Menu Mode The system provides a Temporary Schedule for each partition Enter the temporary scheduling mode by pressing Installer Code 81 Fill in the required data on the...

Страница 55: ...ERVISORY 5 OUT 2 FIRE 6 OUT 5 REMOTE KEYPAD SOUNDER 7 OUT 1 OPEN CLOSE 8 GROUND 9 IN 1 N O LOOP RATINGS OUT 1 5 7 LOW 2K TO GROUND HIGH 10 14VDC 20mA MAX OTHER OUTS LOW 1K TO GROUND HIGH 10 14VDC THRU...

Страница 56: ...9 l K3840V1 9 00 165 Eileen Way Syosset NY 11791 Copyright 2000 PITTWAY Corporation www PDF Zoo com...

Отзывы: