EURODIM TWIN TECH
Installation manual - Page 24
Version 1.2
6.1 Outputs to the loads
The cabling compartment with output terminals is on the right hand side. The load terminals
are mounted next to the relevant module. The numbering is shown on self-adhesive labels.
These terminal blocks are suitable for cable sizes up to 10 mm². Special Adaptors are
available for cables up to 25 mm² when installing 10 kW circuits. Grey = L ; blue = N.
The load cables must be sized in accordance with local regulations. Increased sizes may be
required in order to reduce the voltage drop on the line to the luminaire. We suggest limiting
the voltage drop to 3%.
Pay attention when fasting the load cables and tightening the terminal screws!
Do not over tighten the screws, do not use power tools (e.g. electric drill machines)
– this
may damage the terminals, and they will need to be replaced. This is a time consuming
operation!
The data cables may follow the power cables on the condition that they are minimum
250 mm apart or in a separate shielded trunking (e.g. steel tube). Sound and video cables
must be kept at a minimum distance of 500 mm from all power cables. If cables or ducts
have to cross, then a crossing at right angles will reduce interferences.
6.2 Identification of the dimmers
The dimmers in a cabinet are identified by [slot number].[dimmer in the module].
Example: dimmer 2.3 is the third dimmer in the second module of the cabinet.
The pre-
printed label also shows the module’s supply phase. Custom labelling of the
terminals is possible, e.g. the outlet or channel number.
6.3 Load terminals for 4 x 2.5 / 3 kW modules
Use all four pairs (L+N) of output terminals.
Please also see drawing N° 3500.01.650
6.4 Load terminals for 3 x 5 kW modules
Use only the first three pairs (L+N) of output terminals.
Do not use the fourth pair, labeled x.4.
6.5 Load terminals for 2 x 3 kW fluo modules
Each fluo dimmer comes with a dimmed output and a direct output on the second set of
output terminals. This can be compared to a standard 4 x 3 kW module. All 4 circuits need to
be patched to a DMX adress.
Your Fluo circuitry should be connected as follows:
- fluo dimmer 1 DIM: dimmed phase output on output e.g. 15.1 LINE
- fluo dimmer 1 DIM: dimmed neutral output on output e.g. 15.1 NEUTRAL
- fluo dimmer 2 DIM: dimmed phase output on output e.g. 15.2 LINE
- fluo dimmer 2 DIM: dimmed neutral output on output e.g. 15.2 NEUTRAL
- fluo dimmer 1 DIRECT: direct phase output on output e.g. 15.3 LINE
- fluo dimmer 1 DIRECT: direct neutral output on output e.g. 15.3 NEUTRAL
- fluo dimmer 2 DIRECT: direct phase output on output e.g. 15.4 LINE
- fluo dimmer 2 DIRECT: direct neutral output on output e.g. 15.4 NEUTRAL
etc…
Содержание EURODIM TWIN TECH
Страница 1: ...Installation Manual V 1 2 EURODIM Twin Tech M 3213 1106 03 213 Lighting Technologies ...
Страница 2: ......
Страница 6: ...EURODIM TWIN TECH www adblighting com Installation manual Page 4 Version 1 2 2 DESCRIPTION ...
Страница 48: ...EURODIM TWIN TECH www adblighting com Installation manual Page 46 Version 1 2 11 6 10 kW Module Connection ...
Страница 61: ...EURODIM TWIN TECH www adblighting com Installation manual Page 59 Version 1 2 Notes ...
Страница 62: ...EURODIM TWIN TECH www adblighting com Installation manual Page 60 Version 1 2 Notes ...
Страница 63: ......
Страница 65: ...EURODIM Twin Tech SF 3213 1106 03 213 Lighting Technologies Quick Start Guide Issue 1 0 ...
Страница 66: ......
Страница 83: ...www adblighting com Quick Start page 17 Issue 1 0 6 Menu Tree Structure ...
Страница 98: ...www adblighting com Quick Start page 32 Issue 1 0 Personal Notes ...
Страница 99: ......
Страница 101: ...User Manual V 1 1 EURODIM Twin Tech M 3213 1106 53 213 Lighting Technologies ...
Страница 102: ......
Страница 161: ...EURODIM TWIN TECH www adblighting com User Manual Page 59 Issue 1 1 39 1 Errors List Screen Page Warning message ...
Страница 165: ......