Superheat Adjustment
2
DKRCC.PI.AN0.A4.02 / 520H2448
© Danfoss A/S (AC-BNM/mr), 01 - 2008
SS = 2°C (3.6°F) or according
to customer specifi cation
Number of turns
from SS to
tight
spring
Number of turns
from SS to
loose
spring
R22
+7.25
–4.25
R410A
+9.5
–2
Detail “A”
Superheat
Adjustment
Spindle
Protective Cap
- 1/4
Turn
+ 1/4
Turn
© Danfoss A/S (AC-BNM/mr), 01 - 2008
DKRCC.PI.AN0.A4.02 / 520H2448
1
Instructions
TR 6
067R9508
067R9508
PS = 42 bar /( MWP = 610 psig)
p
test
= max. 47 bar (680 psig)
Reverse: B
→
A
Normal: A
→
B
Flow direction:
Q
nom.
A
→
B [kW] = 100%
Q
nom.
B
→
A [kW] = 80%
Adjustable setting
Fixed setting
Capillary Bulb
Valve Body
Capillary Tube
Protective Cap
A
= 19mm (3/4”)
T = 10Nm (7 ft-lbf)
Superheat Adjustment
• If superheat is lower than 2k = turn Adjustment Spindle , stabilize system for 20 minutes, adjust if required.
• If superheat is highier than 8k = turn Adjustment Spindle , stabilize system for 20 minutes, adjust if required.
See Diagram Below:
1/4
+
1/4
THERMAL EXPANSION VALVE (TXV) ADJUSTMENT
Subcool Adjustment
(Refer Subcool Adjustment to Refrigerant Charging Section).
REFRIGERANT CHARGING
Allow the systems to stabilize for 20 minutes before adjusting the thermal expansion valve (TXV) in order to
ensure correct subcooling and superheat conditions. Turn Superheat Adjustment spindle 1/4 turn at a time,
stabilizing the systems in between adjustment, check condition, adjust again if necessary until correct subcool
and superheat conditions are attained.
CAUTION